Caution: the following search path and fault resolution is intended for customer service and qualified personnel for
installation/maintenance.
Error Reporting
Fault detected on the keyboard
Failure of the system to dialogue with
an already recognised element
The panel does not communicate
with the other elements of the
system
Generic error of the generator board
This can mean:
- The generator overheated
- Low power supply voltage
- Thermistor breakdown
Temperature probe error
The boiler is still at optimal pressure
level
NUVOLA SMART POWER 110-140-180
All manuals and user guides at all-guides.com
What happened?
Reason
Keyboard
Fault on the
malfunction
keyboard
Missing
One of the
communication
devices is not
with one or more
powered or not
devices
connected
Missing
One of the
communication
devices is not
with one or more
powered or not
devices
connected
Internal error of
the generator
Miscellaneous
board
Panel
temperature
probe problem
The boiler stayed
The exhaust
at optimal
valve is not
pressure level for
working
too long
64
Solution
11. Cut off the electrical
power supply to the
product
2. After a few seconds
restore the power supply
3. If the error persists
please contact your
service centre
1. check the connection of
the devices.
2. if the problem persists
please contact your
service centre
1. check the connection of
the devices.
2. if the problem persists
please contact your
service centre
Contact the service centre
Contact the service centre HIGH
1. check that the exhaust
route is free
2. check that the steam
pipe is not clogged,
folded and does not
siphon
3. clean the exhaust valve.
Error priority
MAXIMUM
HIGH
HIGH
Overheating
(AVERAGE)
Low power
supply voltage
(AVERAGE)
Thermistor
breakdown (LOW)
LOW