7.2 Parameter settings
To change individual parameter settings, see the PLC Settings Manual. Below are parameter settings discussed
in Chapter 5 Use.
7.2.1 SSR_Time
Menu for setting the SSR timer. The SSR timer is for the amount of time before the unit goes from Idling mode to
Standby mode when the pilot signal disappears.
SSR_Time
1/1
T
= 10:00m
Ta = 00:00
7.2.2 DIR_Time
Menu for setting the DIR timer. The DIR timer is the amount of time before the unit goes from Running mode in-
to Idling mode when the pilot signal disappears.
DIR_Time 1/1
T
= 10:00s
Ta = 00:00s
7.2.3 Weekly timer
Weekly timer sets the unit to "Stand By" mode and "Off Mode" at preset times. If the pilot signal "PS" is active
and the Vacuum unit is in Standby mode, the unit starts. Users must be informed about the settings and the
function of the weekly timer if it is used.
WeekTmr
1/2
D1
= - - - - - - -
On1
= -- : --
Off1
= -- : --
D2
= - - - - - - -
On2
= -- : --
FlexPAK DX
T=12:00 minutes: Time before SSR_Time is activ-
ated. The default setting is 12 minutes. The minimum
setting is 5 minutes.
Ta=00:00 minutes: The elapsed time since the pilot
signal disappeared.
ESC
OK
T=10:00 seconds: Time before DIR_Time is activ-
ated. The default setting is 10 seconds The minimum
setting is 5 seconds.
Ta=00:00 seconds: The elapsed time since the pilot
signal disappeared.
ESC
OK
ESC
OK
EN
33