5.3.13
UL-compliant installation
REMARQUE
Le chapitre suivant est toujours en anglais, indépendamment de la langue de la pré-
sente documentation et ce en raison des prescriptions UL.
Field Wiring Power Terminals
Observe the following notes for UL-compliant installation:
Short Circuit Current Rating
Suitable for use on a circuit capable of delivering not more than 200,000 rms symme-
trical amperes when protected as follows:
For 240 V systems:
250 V minimum, 25 A maximum, non-semiconductor fuses
or 250 V minimum, 25 A maximum, inverse time circuit breakers
For 500 V systems:
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below.
Series
MOVIFIT
Motor Overload Protection
MOVIFIT
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 140% of the rated motor current.
Device and Line Protection
MOVIFIT
provided with device protection and line protection.
Use 75 °C copper wire only
MOVIFIT
®
uses cage clamp terminals.
MOVIFIT
®
-FC, max. voltage is limited to 500 V.
non-semiconductor fuses
®
-FC
500 V minimum, 25 A maximum
®
-FC is provided with load and speed-sensitive overload protection and ther-
®
-FC: Units in connection with ABOXes MTA...-M11-.. or MTA....-M12-.. are
Installation électrique
Consignes d'installation (toutes exécutions)
inverse time circuit breaker
500 V minimum, 25 A maximum
Notice d'exploitation – MOVIFIT
5
55
®
FC