LERBAKKEN 10, 8410 ROENDE DENMARK
For safe installation of associated apparatus 9116Bx the following must be observed. The module
shall only be installed by qualified personnel who are familiar with the national and international
laws, directives and standards that apply to this area
For Installation in DIV2/Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is important
that the module is undamaged and has not been altered or modified in any way. Only 4501
modules free of dust and moisture shall be installed.
9116A1-U9, 9116B1-U9: Universal Converter Voc or Uo: 28V
9116A2-U9, 9116B2-U9: Universal Converter Voc or Uo: 21.4V
Marking:
Proc. Cont. Eq. for Use in Haz. Loc.
Install in CL I DIV2 GP A-D T4 provide
IS circuits to CL I-III DIV 1 GP A-G
or CL I Zn2 Gp IIC T4 provides IS
E233311
circuits for CL I Zn0 Gp IIC/Zn20 Gp IIIC
Um=253V [Exia] Installation Drawing: 9116QU01
Proc. Cont. Eq. for Use in Haz. Loc.
Install in CL I DIV2 GP A-D T4
or CL I Zn2 Gp IIC T4
E233311
Installation Drawing: 9116QU01
Standards:
UL 121201 NONINCENDIVE ELECTRICAL EQUIPMENT FOR USE IN CLASS I AND II,
DIVISION 2 AND CLASS III, DIVISIONS 1 AND 2 HAZARDOUS (CLASSIFIED) LOCATIONS
Edition 9 - Revision Date 2018/08/31
CSA C22.2 NO. 213 NONINCENDIVE ELECTRICAL EQUIPMENT FOR USE IN CLASS I
AND II, DIVISION 2 AND CLASS III, DIVISIONS 1 AND 2 HAZARDOUS (CLASSIFIED)
LOCATIONS- Edition 3 - Issue Date 2017/09/01
UL 913 STANDARD FOR INTRINSICALLY SAFE APPARATUS AND ASSOCIATED
APPARATUS FOR USE IN CLASS I, II, III, DIVISION 1, HAZARDOUS (CLASSIFIED)
LOCATIONS- Edition 8 - Revision Date 2015/10/16
CSA C22.2 NO. 60079-0 EXPLOSIVE ATMOSPHERES — PART 0: EQUIPMENT —
GENERAL REQUIREMENTS- Edition 3 - Issue Date 2015/10/01
CSA C22.2 NO. 60079-11:14 EXPLOSIVE ATMOSPHERES — PART 11: EQUIPMENT
PROTECTION BY INTRINSIC SAFETY "I"- Edition 2 - Issue Date 2014/02/01
Revision date:
2019-11-26
44
UL Installation drawing
Version Revision
V1 R0
9116 - Version de produit 9116-003
9116QU01
The 9116Bx is galvanically isolating
associated apparatus for installation in non-
hazardous locations or Class I, Division 2,
Groups A – D hazardous locations with
intrinsically safe connections to Class I, II and
III hazardous locations.
The 9116Ax is intended for installation in
non-hazardous locations or Class I,Division
2, Groups A – D or Zone 2 Croup IIC
hazardous locations.
Prepared by:
PB
Page:
1/7