PR electronics A/S tilbyder et bredt program af analoge og digitale signalbehandlingsmoduler til industriel automation. Programmet består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere, Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv barske miljøer med elektrisk støj, vibrationer og temperaturudsving, og alle produkter opfylder de strengeste internationale standarder.
Graphique descriptif de la fonction consigne ......32 Appendix ....................33 IECEx Installation Drawing .............. 34 ATEX Installation Drawing ............... 38 FM Installation Drawing ..............42 INMETRO Installation Drawing ............46 Safety Manual ..................50 9116 - Product Version 9116-003...
Page 4
électrostatiques (ESD) : Montage général, raccordement et débranchement de fils. Recherche de pannes sur le module. Seule PR electronics SARL est autorisée à réparer le module et à remplacer les fusibles. AVERTISSEMENT Ne pas ouvrir la plaque avant du module au risque d’endommager le connecteur de l’indicateur / la façade de programmation PR 4501.
Page 5
Ce bouton doit être étiqueté avec la mention : peut couper la tension du module. Pour une installation sur le rail d’alimentation 9400, le module sera alimenté par le contrôleur d’alimentation 9410. 9116 - Product Version 9116-003...
Page 6
PR electronics SARL, même si cette dernière figure dans l’accord de vente conclu. DEMONTAGE DU SYSTEME 9000 Figure 1 : Débloquez le verrou inférieur pour dégager le module du rail d’alimentation. 9116 - Product Version 9116-003...
/ ou un signal électronique collectif par le rail d’alimentation. • Le 9116 a été conçu, développé et certifié pour utilisation dans les applications SIL 2 en conformité avec les exigences de la CEI 61508. Caractéristiques techniques • 1 LED verte et 2 LED rouges en face avant indiquent un fonctionnement normal ou incorrect du module. 1 LED jaune indique l’état du relais. • Isolation galvanique de 2,6 kVca entre l’entrée, la sortie et l’alimentation. 9116 - Product Version 9116-003...
Etat du module N.F. Etat du module Alimentation Zone 0, 1, 2, par rail 20, 21, 22, M1 / Cl. I/II/III, div. 1 Zone 2 / Cl. 1, div. 2, gr. A-D ou zone non-dangereuse gr. A-G 9116 - Product Version 9116-003...
4 affiche l’etat du relais et de communication ainsi que l’état SIL (ouvert / ver- rouillé). Point statique = verrouillage SIL, point clignotante = aucun verrouillage SIL. • L’accès à la programmation peut être bloqué par un mot de passe. Ce mot de passe est sauvegardé dans le module afin d’assurer un haut niveau de protec- tion contre les modifications non autorisées. 9116 - Product Version 9116-003...
1 : Insérez les crochets du 4501/4511 dans les trous en haut du module. 2 : Poussez le bas du 4501/4511 vers le module. Démontage du 4501/4511 3 : Appuyez sur le bouton de déclenchement en dessous du 4501/4511, puis tirez le 4501/4511 vers le haut. 9116 - Product Version 9116-003...
/ AWG 26...14 fil multibrins Pression max. avant déformation de la vis ................ 0,5 Nm Vibration ..............IEC 60068-2-6 : 2007 Vibration : 2...13,2 Hz ..........±1 mm Vibration : 13,2...100 Hz ........±0,7 g 9116 - Product Version 9116-003...
Page 12
Interface de communication........ Interface de communication 4511 Façade de programmation 4501 Rapport signal / bruit ..........Min. 60 dB (0...100 kHz) Temps de réponse (0...90%, 100...10%) : Entrée température, programmable ..1...60 s Entrée mA / V, programmable ....0,4...60 s 9116 - Product Version 9116-003...
Page 13
Type TC : B 160...400°C ≤ ±4,5°C ≤ ±0,45°C / °C Type TC : B ≤ ±2°C ≤ ±0,2°C / °C 400...1820°C Immunité CEM.............. < ±0,5% de l’EC Immunité CEM améliorée : NAMUR NE 21, critère A, burst ........ < ±1% de l’EC 9116 - Product Version 9116-003...
Page 15
Stabilité de charge ..........≤ 0,01% de l’EC / 100 Ω Résistance de charge ..........≤ (V -3,5) / 0,023 A [Ω] alimentation Gamme d’alimentation externe pour transmetteur 2-fils........3,5...26 Vcc Effet d’une variation de la tension d’alimentation externe 2-fils ...... < 0,005% de l’EC / V 9116 - Product Version 9116-003...
Page 16
FM us ................. 3038267-C INMETRO ..............NCC 12.1309 X CCOE ................P337349/4 EAC Ex TR-CU 012/2011 ........RU C-DK.GB08.V.00410 Sécurité fonctionnelle : Certifié SIL2 en « Evaluation Complète » selon IEC 61508 EC = Echelle configurée 9116 - Product Version 9116-003...
LIN.R Pour R lin._0%≥ env. 18 Ω SE.SH Court circuit capteur Rupture capteur ou Tous SE.BR resistance de ligne trop haute TEMP Pt100 à Pt1000 et Ni50 à Ni1000 SE.SH Court circuit capteur 9116 - Product Version 9116-003...
Erreur aliment. du CPU prin.* Erreur matériel MP.ER Erreur ProgFlow du CPU prin.* Erreur de l’autotest d’initialisation Erreur matériel MI.ER principale Erreur matériel DE.ER Erreur du module* Somme de contrôle de code non Erreur matériel FC.ER valable en 4501 9116 - Product Version 9116-003...
Page 19
OK. L’erreur est corrigée en déconnectant et puis reconnectant l’alimentation du module. ** L’erreur peut être négligée en sélectionnant un type d’entrée autre que TC. *** L’erreur est corrigée en parcourant les menus. 9116 - Product Version 9116-003...
Relais de sortie exité Fermé Clignotante Clignotante Désexcité par court circuit / rupture (si activé) Relais de sortie désexité Fermé Clignotante Clignotante Désexcité par court circuit / rupture (si activé) Relais de sortie désexité Clignotante Excité Ouvert 9116 - Product Version 9116-003...
Page 23
OPERATION DES TOUChES DE FONCTION Documentation pour le diagramme de programmation. Généralités Lors de la configuration du 9116 vous êtes guidés tout au long des paramètres du menu ; ainsi vous pouvez choisir le réglage qui correspond à votre application. Pour chaque menu il y a un texte d’aide qui défile en ligne 3 de l’indicateur.
Page 24
Le relais est désactivé. Croissant / Décroissant : Le relais peut être actif en mode croissant ou décroissant. Délais : Fonctions Délai “ON” ou “OFF” peuvent être choisies pour le relais entre 0...3600 s. hystérésis : L’hystérésis peut être configuré entre 0,1 et 25% de l’échelle ou entre 1 et 25 % de la gamme d’affichage. 9116 - Product Version 9116-003...
Page 25
à l’aide des flèches et ainsi contrôler le signal de sortie haut et bas ou l’état du relais OFF et ON. Vous devez sortir du menu en pressant 3 (pas de time-out). La simulation sera terminée, si le 4501 est enlevé. 9116 - Product Version 9116-003...
Page 26
Rail d’alimentation : Dans le menu ”RAIL” vous pouvez choirsir si des erreurs capteur doivent être transmis à l’unité de surveillance du module PR 9410 Contrôleur d’alimentation. Safety Integrity Level (SIL): Voir le ”Safety Manual” (en Anglais) pour information supplémentaire. 9116 - Product Version 9116-003...
Sélectionner Fonction POWER - le relais indique état [54] Permettre protection par mot de passe ? d’alimentation OK [55] Entrer Nouveau mot de passe Sélectionner Fonction ERREUR - le relais indique [56] Permettre la fonctionalité Réglage rapide ? uniquement erreur capteur 9116 - Product Version 9116-003...
Page 32
Erreur dans la mémoire FLASH - contrôler la configuration [89] Configuration ou version invalide [90] Erreur matériel [91] Erreur du capteur CSF - contrôler la température du module [92] Erreur CSF - contrôler le bornier CSF [93] Pas de communication 9116 - Product Version 9116-003...
Graphique descriptif de la fonction consigne Signal Délai ON d’entrée Délai OFF Consigne (croissante) Hystérésis Temps Relais On Fermé Contact (N.O.) Ouvert 9116 - Product Version 9116-003...
APPENDIx IECEx Installation drawing ATEx Installation drawing FM Installation drawing INMETRO Installation drawing Safety manual 9116 - Product Version 9116-003...
Page 36
For Installation in Zone 2 the following must be observed. The 4501 programming module is to be used solely with PR electronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.
Page 37
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed. Revision date: Version Revision Prepared by: Page: 2012-07-04 V6 R0 9116 - Product Version 9116-003...
Page 41
Pour l'installation avec le rail d’alimentation dans la zone 2, on doit utiliser seulement le rail d’alimentation type 9400 ainsi que le contrôleur de puissance type 9410 (Attestation d’examen de type KEMA 07ATEX0152 X). Revision date: Version Revision Prepared by: Page: 2012-07-04 V6 R0 – FR01 9116 - Product Version 9116-003...
For Installation in Zone 2 / Division 2 the following must be observed. The 4501 programming module is to be used solely with PR electronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.
Page 45
Warning: Do not mount or remove modules from the Power Rail when an explosive gas mixture is present. Revision date: Version Revision Prepared by: Page: 2012-06-08 V6 R0 9116 - Product Version 9116-003...
Page 46
IIC or A,B Io, Isc 93 mA 1.13 μF 16 mH 218 μH/Ω IIB or C,E,F 650 mW 4.15 μF 32 mH 436 μH/Ω IIA or D,G Revision date: Version Revision Prepared by: Page: 2012-06-08 V6 R0 9116 - Product Version 9116-003...
Page 47
IIC or A,B Io, Isc 0.2 mA 2.3 μF 100 mH 100mH/Ω IIB or C,E,F 0.8 mW 9.5 μF 100 mH 200mH/Ω IIA or D,G Revision date: Version Revision Prepared by: Page: 2012-06-08 V6 R0 9116 - Product Version 9116-003...
Page 48
Corrente máx.:: 2 A AC / 2 ADC (terminais 11,12,13,14) 9116 RTD / LinR (terminais 31,32,33,34) (terminais 91,92,93,94,95) : 253 V; máx. 400 Hz TRILHO DE ENERGIA Revision date: Version Revision Prepared by: Page: 2013-05-31 V6 R0 9116 - Product Version 9116-003...
Page 49
Para a instalação de trilho de energia na Zona 2, apenas o trilho de alimentação Rail 9400 fornecido pela Unidade de Controle de Potência 9410 é permitido. Revision date: Version Revision Prepared by: Page: 2013-05-31 V6 R0 9116 - Product Version 9116-003...
Safety manual unIVeRSal COnVeRteR 9116 this safety manual is valid for the following product versions: 9116-003 9116-002 9116-001 Version No. V3R0...
Page 53
9116 Universal converter safety Manual 0 COntentS 1 Observed standards ..................... 2 Acronyms and abbreviations ..................3 Purpose of the product ....................4 Assumptions and restrictions for use of the product ..........4.1 Basic safety specifications .................. 4.2 Safety accuracy ....................
Error events, including cable faults, are monitored and signalled via the individual status relay and/or a collective electronic signal via the power rail. The 9116 has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Safety Manual 9116 UniverSal converter assumptions and restrictions for use of the product Basic safety specifications Operational temperature range....-20...+60°C Storage temperature range...... -20...+85°C Power supply type, min......Double or reinforced Supply voltage ......... 19.2...31.2 VDC Relay output pulse length, min....70 ms Loop supply ..........
Refer to section 14 - Safe parameterisation - user responsibility. 4.3.4 analogue output The connected safety PLC shall be able to detect and handle the fault indications on the analogue output of the 9116 converter by having a NAMUR NE43-compliant current input. 4.3.5 Relay output The relay output shall only be connected to equiment which has a current limiting function of 2 A.
Safety Manual 9116 UniverSal converter For RTD and linear resistance input sensors, cable resistances of up to 50 W per wire can be compensated if 3- or 4-wire connection is configured. For thermocouple sensors, cold junction temperature errors can be compensated, either by an internally mounted temperature sensor, or by an accessory connector with a built-in temperature sensor.
Relay lifetime (Note 2 ) 100 000 times Note 1 : The 9116 contains no lifetime limiting components, therefore the PFH figures are valid for up to 12 years, according to IEC 61508. Note 2 : The user must calculate the product lifetime with regard to the relay lifetime.
Any failures that are detected and that compromise functional safety should be reported to the sales department at PR electronics A/S. Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only. 12 maintenance No maintenance required.
Safety Manual 9116 UniverSal converter 13.2.2 Sensor/cable fault information via display front 4501 When the function is enabled and supported by selected input type, sensor or cable faults are displayed as SE.BR (sensor break) or SE.SH (cable short-circuited). In case of sensor or cable fault the backlight flashes. This can be reset by pressing the 3 key.
9116 Universal converter safety Manual 13.3.7 Simulation (SIm) It is possible to override the actual measured input signal by a simulated value. In the REL.SIM menu it is posible to simulate the relay state with out affecting the analogue output, by pressing .
Page 65
9116 Universal converter safety Manual CONNEC Selected sensor connection type for RTD or linear resistance measurements (for SENSOR = Ni or Pt or IN.TYPE = LIN.R): 2W = 2-wire 3W = 3-wire 4W = 4-wire If 2W or 3W is selected, the end user must ensure that the applied sensor wiring does not introduce failures exceeding the requirements for the safety application.
Safety Manual 9116 UniverSal converter 14.1.2 Parameters related to Relay Output REL.UNI Relay Units (for IN.TYPE ≠ TEMP): PERC = Relay setpoint in percent of input range. DISP = Relay setpoints and hysteresis values relates to DISP.LO and DISP.HI (display units) REL.FUN...
9116 Universal converter safety Manual ERR.ACT Relay sensor error action (for REL.FUN = SETP, WIND or ERR): Only relevant if IN.TYPE = TEMP, CURR and I.RANGE = 4-20, POTM or LIN.R and R 0% is ≥ 18. NONE (Note 3 ) = Sensor error detection NOT enabled (Note 4 ), relay state at sensor error is undefined.
Safety Manual 9116 UniverSal converter OUT.LO Selected temperature value for 0% output for IN.TYPE = TEMP in units defined by the UNIT parameter (°C or °F) Range is defined by the selected temperature sensor (SENSOR and TC.TYPE, Ni.TYPE or Pt.TYPE), but value must be less than OUT.HI - minimum span.
9116 Universal converter safety Manual 14.2.1 If no password is set action Display shows Press OK ADV.SET Set (ADV.SET) to Yes and press OK SETUP Set SETUP to SIL and press OK EN.SIL Set EN.SIL to YES and press OK NEW.PAS...
Page 70
Safety Manual 9116 UniverSal converter Action Display shows Verify CJC type and press OK V.RANGE (ONLY if IN.TYPE = TEMP and SENSOR = TC) Verify fixed input voltage range and press OK R 0% (ONLY if IN.TYPE = VOLT) Verify input resistance 0% range and press OK R 100% (ONLY if IN.TYPE = LIN.R)
Page 71
9116 Universal converter safety Manual Action Display shows Verify relay activation direction and press OK HYST (ONLY if REL.FUN = SETP) Verify relay setpoint hysteresis and press OK ERR.ACT (ONLY if REL.FUN = SETP or WIND) Verify relay action on sensor error and press OK ON.DEL...
(and sensor, if applicable) are tested. 15 fault reaction and restart condition When the 9116 detects a fault the outputs will go to Safe State, in which the outputs will be “de-energised”. If the fault is application-specific (cable error detection) the 9116 will restart when the fault has been corrected.
9116 Universal converter safety Manual 16 user interface [01] Set correct password [19] Select OFF function - relay is permanently off [02] Enter Advanced setup menu? Select POWER function - relay indicates power [03] Select Temperature input status OK Select Potentiometer input...
Page 74
Safety Manual 9116 UniverSal converter [58] Relay setpoint - Read only [59] Select Language [60] Use process calibration values? [61] Set value for low calibration point [62] Set value for high calibration point [63] Enable Rail status signal output? [64] Enable SIL configuration lock? 0...20 mA is not a valid output range for SIL operation...
Page 75
9116 Universal converter safety Manual 16.2 Routing diagram Power up Fast setpoint adjustment and relay test 50.0 1 Increase setpoint SETP. 2 Decrease setpoint Txt 57 3 Save and exit the menu 1 and 2 simultaneously = change relay state ...
Safety Manual 9116 UniverSal converter ROutInG DIaGRam If no key is activated for 1 minute, the display will return to the default state 1.0 without saving configuration changes. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Accept the chosen value and proceed to the next menu Hold 3 Back to previous menu / return to menu 1.0 without saving...
9116 Universal converter safety Manual 17 Connections diagram Power Rail Supply and connections status relay 91 92 93 94 95 31 32 33 34 N.C. Gnd. Gnd. +24 V Error signal +24 V NC = no connection Inputs: *TC, TC, internal CJC...
Page 80
Displays Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearization, scaling, and difference measurement functions for programming via PReset software. Ex interfaces Interfaces for analog and digital signals as well as HART signals between sensors / I/P converters / ®...