Ul Control Drawing 5104Qu01 - PR electronics 5104 Mode D'emploi

Table des Matières

Publicité

UL CONTROL DRAwING 5104QU01

Hazardous (Classified) Location
Class I, Division 1, Group A,B,C,D
Class I , Zone 0 and 1, Group IIC
Class II, Division 1 Group E, F, G
Intrinsically safe apparatus
entity parameters:
Vmax. (Ui) ≥ Vt (Uo)
≥ It (Io)
Imax. (Ii)
Pi ≥ Po
Ca ≥ C cable + Ci
La ≥ L cable + Li
The sum of capacitance and
inductance of cable and
intrinsic safe equipment must
be less or equal to Ca and La
Installation notes:
1) The maximum nonhazardous location voltage is 250VAC/DC.
2) The installation shall be in accordance with the National Electrical Code
NFPA 70, Articles 504 and 505.
3) The terminals of the two individual channels shall not be interconnected in any
way.
4) Install in Pollution degree 2 or better
5) Use 60 / 75 °C copper conductors with wire size AWG: (26 – 14).
6) Warning: Substitution of components may impair intrinsic safety.
+
T
-
+
+
T
V
+
-
-
-
+
V
-
+
+
T
V
+
-
-
-
5104B Associated apparatus parameters
CH1
Terminals 41 to 44
CH2
Terminals 51 to 54
Vt Uo)
28 V
It (Io)
93 mA
Po
0.65 W
IIC / grp. A,B IIB / grp. C IIA / grp.D
0.052 μF
Ca (Co)
La (Lo)
2.4 mH
51 0 4 V 1 0 4 - FR
Nonhazardous
Associated apparatus
Galvanically Isolated
31
33
44
14
43
13
42
12
41
11
CH1
Output
24
54
53
23
52
22
21
51
5104B
CH2
Output
0.44 μF
1.45 μF
12 mH
20 mH
Rev. AA 2003-02-12
+
2-wire
installation
m A
I +
m A
m A
V +
V
V
I +
I
V
I+V
Output
Output
+
2-wire
installation
m A
I +
m A
m A
V +
V
V
I +
I
V
I+V
Output
Output
15

Publicité

Table des Matières
loading

Table des Matières