LERBAKKEN 10, 8410 RØNDE DENMARK
For safe installation of 9107 the following must be observed. The module shall only be
Installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
9107BA:
9107BB:
IECEx Certificate: .................. IECEx DEK 11.0088X
Marking 9107Bx
Marking 9107Bx, 9107Ax
Standards
Supply terminal (31,32)
Voltage:
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
Installation notes:
Install in pollution degree 2, overvoltage category II as defined in IEC 60664-1
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Disconnect power before servicing.
The wiring of unused terminals is not allowed.
In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements
shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152) is allowed.
Revision date:
2020-06-18
IECEx Installation drawing
HART
-transparent driver
1 channel
HART
-transparent driver
2 channel
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc
IEC60079-11:2011, IEC60079-0: 2017, IEC60079-15 :2017
IEC60079-7: 2015+A1:2017
19.2 – 31.2 VDC
125VAC / 110VDC
62,5VA / 32W
0.5A AC / 0.3ADC
Version Revision
V4 R0
9107 - Version de produit 9107-002
9107QI01
Zone 2 Installation
32VAC / 32VDC
16VA / 32W
0.5A AC / 1ADC
Prepared by:
PB
Page:
1/3