LERBAKKEN 10, 8410 RØNDE DENMARK
9107Ax, 9107Bx Installation:
Hazardous area
Zone 2
Output
CH1 (terminal 41,42)
CH2 (terminal 51,52)
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n
or Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking
elements shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Certificate IECEx KEM 08.0025X) is allowed.
For Installation in Zone 2 the following must be observed. The 4501 programming module is to be
used solely with PRelectronics modules. It is important that the module is undamaged and has not
been altered or modified in any way. Only 4501 modules free of dust and moisture shall be
installed.
Revision date:
2020-06-18
-20 ≤Ta ≤ +60ºC
44
43
42
+
CH1
mA
41
_
54
53
52
+
CH2
51
mA
_
91 92 93 94 95
Power Rail
125VAC / 110VDC
62,5VA / 32W
0.5A AC / 0.3ADC
Version Revision
V4 R0
9107 - Version de produit 9107-002
4501
34
33
32
31
14
13
12
11
9107
Supply: 19.2 – 31.2 VDC
(terminal 31,32)
(terminal 91,92,93,94,95)
Input:
(terminal 11,12,13,14)
Zone 2 Installation
32VAC / 32VDC
16VA / 32W
0.5A AC / 1ADC
Prepared by:
PB
9107QI01
Page:
3/3
23