Supervisory Control Wiring; Interconnection Diagram - Briggs & Stratton 200 SED Serie Guide D'installation Et De Démarrage Rapide

Commutateur de transfert automatique double 200 a – 400 fractionné avec service de déconnexion et module de contrôle c.a.
Masquer les pouces Voir aussi pour 200 SED Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Supervisory Control Wiring

An air conditioner can be used with the supervisory contacts
on either terminals A-A or B-B. Terminals A-A can only be
used with supervisory control. Large loads can only be used
with contactor control on terminals B-B. Examples of each
system are described below.
1. The terminal strip on control module in transfer switch
has four connections for customer use. There are two
sets of "Normally Closed" contacts available. They will
be activated when generator power is required. These
can be used for supervisory control of large connected
loads on generator. Loads will be allowed to operate if
there is enough generator power available.
NOTE: There are two wireways provided to keep the
supervisory loads separated from each other.
2. Terminals "A-A" on control module are rated for
24 VAC and air conditioner contactor control. Contacts
are connected in series with the air conditioner
contactor control circuit.
Air Conditioner Contactor
A
A
3. Terminals "B-B" on control module are rated for 1 Amp
125 VAC and installer supplied contactor to control
a large load, such as an electric hot water heater.
Contacts are connected in series with the contactor
control circuit.
B
B
4. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure for proper
torque values.
10
24 VAC
Contactor
Neutral
120 VAC

Interconnection Diagram

The illustration on the following pages shows a completed transfer
switch installation. Your actual layout may vary.
Illustration callouts are:
A1 - From Utility to First Service Panel
A2 - From Utility to Second Service Panel
B1 - Current Transformer
B2 - Current Transformer
C - T/R and GND to Generator
D - CT Terminals
E - Transfer Switch Contactors
F - UTILITY 240VAC to Generator
G1 - Transfer Switch Neutral Terminal
G2 - Transfer Switch Neutral Terminal
H - Generator
J - Generator Ground Terminal
K - Generator Neutral Terminal
L - Generator Circuit Breaker
M - Ten pin Connector or Ten pin terminal
N - Two pin Connector or Two pin terminal
P1 - Main Distribution Panel 1
P2 - Main Distribution Panel 2
R1 - Distribution Panel Neutral Bus
R2 - Distribution Panel Neutral Bus
S1 - Distribution Panel Ground Bus
S2 - Distribution Panel Ground Bus
T1 - Transfer Switch Ground Terminal
T2 - Transfer Switch Ground Terminal
U1 - Load Connections to Distribution Panel
U2 - Load Connections to Distribution Panel
V1 - Service Entrance Breaker - UTILITY 1
V2 - Service Entrance Breaker - UTILITY 2
W - Generator Connection
Y1 - Utility Connection
Y2 - Utility Connection
BRIGGSandSTRATTON.COM

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

200 sed 071058

Table des Matières