Prot. différentielle numérique
10I1REL.
min. 0.00
max. 1.50
10T-DLY.
min. 0.00
max. 60.00
10 HARM2
OFF
ON
10 HARM2
min. 10
max. 80
10IHARM2
min. 1.00
max. 10.00
10INT.TR
OFF
ON
10S.PROL
min. 0.00
max. 5.00
10 I-SpC
min. 0.10
max. 1.00/ì
10 T-Spc
min. 5
max. 60
────────────────────────────────────────────────────────────────────────
11PILOT WIRE MON - PILOT WIRE MONITORING
11PL.MON
ON
OFF
11STATN.
SLAVE
MASTER
11DIF.BL
ON
OFF
11T-PLT.
min. 0.2
max. 60.0
────────────────────────────────────────────────────────────────────────
A-16
SIPROTEC7SD600 V3.1 - Manuel
Min. local current I1 to release trip by DIFF
InL
────
Time delay of differential protection
s
────
State of 2nd harmonic restraint
[ ] off
[ ] on
2nd harmonic contend in the different. current
%
────
Max. diff current for 2nd harmonic restraint
InL
────
State of the intertrip send function
[ ] off
[ ] on
Send signal prolongation for intertrip
s
────
Diff current threshold for Spill Current sup.
InL
────
Time delay for Spill Current supervision
s
────
State of pilot wire monitor function
[ ] on
[ ] off
Station identification
[ ] Slave
[ ] Master
Block. diff. funct. during pilot wire failure
[ ] on
[ ] off
Time delay for blocking the diff. function
s
────
Réf. de commande E50417-G1177-C069-A2
Siemens AG Janvier 2009