Prot. différentielle numérique
Table d'indications pour paramètres de fonctions 7SD600
════════════════════════════════════════════════════════
PARAME. - PARAMETER SETTINGS
00 CONF. - SCOPE OF FUNCTIONS
00PL.MON
nonEXIST
EXIST
────────────────────────────────────────────────────────────────────────
01 POWER SYST.DAT - POWER SYSTEM DATA
01 FREQ
50 Hz
60 Hz
01IN LN.
min. 1
max. 100000
01IctPRI
min. 1
max. 100000
01Rx
min. 0
max. 2000
01 T-TRP
min. 0.01
max. 60.00
01 L.Out
OFF
ON
01L.O.Re
button
bin.inp.
but.o.BI
────────────────────────────────────────────────────────────────────────
10PL.WIR DIF.PROT - PILOT WIRE DIFFERENTIAL PROTECTION
10DIF.PR
ON
OFF
ALRMonly
10IDIFF>
min. 0.50
max. 2.50
Siemens AG Janvier 2009
SIPROTEC7SD600 V3.1 - Manuel
Pilot wire monitor
[ ] Non-existent
[ ] Existent
Rated system frequency
[ ] fN 50 Hz
[ ] fN 60 Hz
Nominal current of line/cable
A
────
Primary rated current of CT
A
────
Pilot wire loop resistance to 2nd line end
Û
────
Minimum trip command duration
s
────
State of Lockout function
[ ] off
[ ] on
Reset of Lockout
[ ] via LED-quit button
[ ] via binary input
[ ] via but. or bin.inp.
State of the differential protection
[ ] on
[ ] off
[ ] Alarm only
Pick-up value of differential current
InL
────
Réf. de commande E50417-G1177-C069-A2
A-15