PR electronics 7501 Manuel De Produit page 50

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LERBAKKEN 10, 8410 RØNDE DENMARK.
Ex nA, ic installation:
Certificate
Marking
Standards:
Type of protection Ex nA
O-ring Sealing : Silicone
T4: -40 ≤ Ta ≤ 85ºC T4 (7501A )
T4: -40 ≤ Ta ≤ 80ºC T4 (7501B )
T6: -40 ≤ Ta ≤ 60ºC T6
O-ring Sealing : FKM
T4: -20 ≤ Ta ≤ 85ºC (7501A )
T4: -20 ≤ Ta ≤ 80ºC (7501B )
T6: -20 ≤ Ta ≤ 60ºC
Hazardous area
Zone 2, 22
Sensor
Terminal: 3,4,5,6
Ex ic
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 45 mH
Co: 28 μF
Revision date:
2015-09-16
50
IECEx DEK 15.0039 X
Ex nA IIC T6...T4 Gc
Ex ic IIC T6...T4 Gc
Ex ic IIIC T100°C Dc
IEC 60079-0: 2011, IEC 60079-11: 2011, IEC 60079-15: 2010
6
+
1
5
-
2
4
3
7501
Version Revision
V2R0
WWW.PRELECTRONICS.COM
Type of protection Ex ic
T4: -40 ≤ Ta ≤ 85ºC T100ºC (7501A )
T4; -40 ≤ Ta ≤ 80ºC T100ºC (7501B )
T6: -40 ≤ Ta ≤ 60ºC T85 ºC
Non Hazardous Area
Supply
Supply
Terminal: 1,2
Ex ic
Ui: 35 VDC
Li: 0 μH
Ci: 2 nF
7501V108-FR
7501QI01
Supply
Terminal: 1,2
Ex nA
Umax : 35 VDC
Page:
3/6

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

7500 serie

Table des Matières