3.4 Termination Cap Clearances

O
Figure 3.5, Minimum Termination Cap Clearances
A
Clearance above grade, veranda, porch, deck, or balcony
B
Clearance to window or door that may be opened
C
Clearance to permanently closed window (recommended to prevent condensation on
window)
D
Vertical clearance to ventilated soffit located above the terminal within a horizontal
distance of 2 feet (61cm) from the center line of the terminal
E
Clearance to unventilated soffit
F
Clearance to outside corner
G
Clearance to inside corner
H
Clearance to each side of center line extended above meter/regulator assembly
I
Clearance to service regulator vent outlet
J
Clearance to non mechanical air supply inlet to building or the combustion air inlet to
any other appliance
K
Clearance to mechanical air supply inlet
L
Clearance above paved sidewalk or paved driveway located on public property
M Clearance under veranda, porch deck, or balcony
N
Clearance between two horizontal terminations
O
Above furnace exhaust or inlet
* Clearance in accordance with local installation codes and the requirements of the gas supplier.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
VINYL SOFFIT, VINYL CEILING, AND VINYL OVERHANG DISCLAIMER: Clearances to heat resistant material (i.e. wood, metal). This does not include vinyl. Hussong
Manufacturing Co., Inc. will not be held responsible for heat damage caused from terminating under vinyl overhangs, vinyl ceilings, or vinyl ventilated/unventi-
lated soffits.
10 FRAMING AND CLEARANCES
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
MEASURE VERTICAL CLEARANCES FROM THIS SURFACE
36"
(914mm)
Canadian installations
12" (30cm)
12" (30cm)
12" (30cm)*
0" (0cm)*
0" (0cm)*
0" (0cm)*
12" (30cm)*
3' (91cm) within a height
15' (4.5 m) above the meter/
regulator assembly
3' (91cm)
12" (30cm)
6' (1.83 m)
7' (2.13 m)†
0" (0cm)‡
12" (30cm)
12" (30cm)
MEASURE HORIZONTAL
CLEARANCES FROM THIS SURFACE
US installations
12" (30cm)
9" (23cm)
12" (30cm)*
0" (0cm)*
0 in (0cm)*
0" (0cm)*
12" (30cm)
*
*
9" (23cm)
3' (91cm) above if within 10' (3
m) horizontally
Massachusetts: 10' (3 m)
*
0" (0cm)
12" (30cm)
12" (30cm)
Kozy Power Vent #KPV R.5