Télécharger Imprimer la page

RIB KING Mode D'emploi page 33

Publicité

Les langues disponibles
  • FR

Les langues disponibles

close position, just before opening, the gate will perform a short closing manoeuvre
(0.5 seconds) to ease unlocking from electric lock.
ELECTrIC LOCK coupling fACILITY
The DIP 10 in the ON position enables the Electric Lock coupling Facility. Once the
gate has closed, a short hammering close pulse (0.5 seconds) will be done at full
power to guarantee the electric lock or mechanical bolt coupling.
f
UNCTIONING Of sAfETY ACCEssOrIEs
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active both in
gate opening and in gate closing. In this configuration, if an obstacle cuts the
photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the
obstacle is removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are active only in
gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still
if a close command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell
receivers must be connected in series.
In case the photocells are not installed, this contact must be short circuited with a
wire jump (from PHOT to COM) to permit the gate to operate.
ATTENTION: In case the receiver led remains lit, malfunctioning of the main
supply is suspected.
It is advisable to connect electrically to earth the
columns or the photocells stands to the terminal D-,
to shield the photocells from external noise.
Be careful not to short circuit the system when the
supply phases are inverted!
AUTOMATIC CLOsING AfTEr THE TrANsIT THrOUGH THE PHOTOCELL
This option could be useful to close automatically the gate when the vehicle left and
disengaged the photocell beam. If the DIP12 is turned ON, this function is activated
and the PHOTO input will have two purposes:
- detect the obstacle and prevent the gate movement in according with the DIP4
position;
- close the gate as soon as the vehicle leaves the photocell beam.
If DIP12 ON and DIP4 Off
If the gate is opening and a vehicle crosses the photo beam, the gate will stop.
When the vehicle leaves, the gate will close automatically after 1 second pause.
If DIP12 ON and DIP4 ON
If the gate is opening and a vehicle crosses the photo beam, the gate will continue
to open. When the vehicle leaves, the gate will stop and then closes automatically
after 1 second pause.
If the complete gate open position is reached before the vehicle leaving, the
DIP12 will be ignored and the automatic closing will be managed in according
to the DIP3 position.
If during closure there is as fast transit (example pedestrian), the gate opens for 2
seconds and then re-close.
PAY ATTENTION: it is highly recommended to check photocells operation at least
every 6 months.
sAfETY sTrIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2 seconds, is
performed. The gate interrupts any movement and this alarm state is indicated by
1 minute Blinker flashing. The normal gate operations can be restored by pressing
any push button or radio commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact.
In case there are more than one safety strip, all their contacts must be connected
in series.
In case the safety strip is not installed, this contact must be short circuited
with a wire jump (from EDGE to COM) to permit the gate to operate and the
safety strip test must be disabled (DIP 13 Off).
fUNCTIONING IN DEAD MAN MODE WHEN THE sAfETY DEVICEs ArE
fAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if
photocell fails or remain engaded for more than 60 seconds, the K BUTTON and
PEDESTRIAN commands will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the
programming led.
With the blinking of the programming led, the opening and closing operation are
allowed only with the command button pressed and held. The radio commands
and that of automatic closing, will be excluded, since their use in this mode, is not
allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio
commands and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the
During the dead-man operation, press and hold the K BUTTON or the PED
BUTTON for the complete operation, and until the switching off of the leds of the
motors (DL3 - DL5 total opening M2 - M1 - pedestrian DL5 - DL4 - DL6 total closing
M2 - M1 - pedestrian DL6), or of the blinker, when installed.
The dead-man operation is only an emergency operation which must be
activated for a very short period and with the complete installation at sight
so to have a secure and safe control of the system. As soon as possible
12Vdc
however, the failing safety devices must be repaired and activated.
Term.
D-
TEsTING THE sAfETY sTrIP equipment
The switch DIP13 ON enables to test the safety strip equipment. The test is
performed every time the gate completes a full opening. The test is available only
if the safety strip device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected to the
D+TEST and D- outputs (DIP13 ON). Automatically, every time the gate completes
a full opening, just before closing, the control board switches OFF the D+TEST and
D- power supply output for a very short time. While the safety strip power supply is
switched OFF, if everything is working fine the safety strip contact (EDGE - COM)
must open. In case the test fails, no other gate manoeuvre will be allowed.
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP13
MUST BE LEFT OPEN.
BLINKEr
Connect the flashing light to the blinker output, use flashing lights ACG7059 and
bulbs of 40W maximum.
PrE-fLAsHING function
The DIP 5 in the ON position enables the pre-flashing, the BLINKER starts flashing
3 seconds before every movement of the gate.
The DIP 5 in the OFF position disables any pre-flashing, the BLINKER starts
flashing and the motors will start at the same time.
BUZZEr
The current supplied to the Buzzer will be 200 mA at 12Vdc.
During the normal operation of the gate, opening and closing, the buzzer will buzz
intermittently. Only during the alarm situations (safety strip) the buzzing will almost
be constant.
GATE OPEN INDICATOr (sIGNAL - COM)
Should you need to have an indication about the leaf position, the output SIGNAL
- COM can be connected to a 12Vdc bulb of 3W maximum. It is turned ON when
the gate is open or partially open, it is turned OFF only when the gate is completely
closed.
33
33
safety strips (or photocells) the photocells (or safety strips) still work by
interrupting the operation in progress.
G
B

Publicité

loading

Ce manuel est également adapté pour:

King wi-fiAd00690Ad00692Ad00691Ad00703