4.2 Application conditions
Ambient temperature:
max. +55 °C
Operating duration:
Unless otherwise indicated on the type label,
the solenoid system is suitable for con-
tinuous operation
Important information for functional reliability during continuous
operation!
If standstill for a long period at least 1-2 activations per day are
recommended.
Service life:
High switching frequency and high pressures
reduce the service life
Permitted medium temperature depending on coil and seal material:
Coil body
Seal material
PA/EP
1)
Polyamide PA
FKM
Epoxy EP (NA38)
FKM
Polyamide PA
EPDM
Epoxy EP (NA38)
EPDM
Polyamide PA
NBR
Marking PA and EP under electric connection
1)
4.3 Conformity
In accordance with the EC Declaration of conformity, the solenoid valve
Type 6213 EV / 6281 EV is compliant with the EC Directives.
4.4 Standards
The applied standards, which verify conformity with the EC Directives,
can be found on the EC Type Examination Certificate and / or the EC
Declaration of Conformity.
4.5 Type label (Example)
Orifice
Circuit function
Type
6213EV A 10 EPDM MS
G3/8
P N0 - 10bar
230V
00221649
Identification number
6
5.2 Before installation
Installation position:
any, actuator preferably upwards.
Procedure:
Check pipelines for dirt and clean.
Install a dirt filter before the valve inlet (≤ 500 µm).
5.3 Installation
NOTE!
Caution risk of breakage!
▶ Do not use the coil as a lifting arm.
Hold the device with a open-end wrench on the body and screw
into the pipeline.
Observe direction of flow:
The arrow on the body indicates the direction of flow.
Medium temperature
0 ... +90 °C
0 ... +120 °C
-30 ... +90 °C
-30 ... +100 °C
-10 ... +80 °C
Seal material
Body material
Connection thread,
operating pressure
50Hz
8W
Voltage, Frequency,
Power consumption
W14 LU
Manufacturer code
english
Permitted media depending on seal material:
Seal material
FKM
Per-solutions, hot oils without additives, diesel
and heating oil without additives, detergent
solution
EPDM
Oil and grease-free liquids, cold and warm
water
NBR
Cold and warm water
Gaseous media at low differential pressures (e.g. compressed air and vacuum)
2)
can also be actuated in consideration (or due to restriction) of a lower tightness.
We recommend prior clarification with our sales office regarding the possible
application
The following values must also be observed for valves with
UL/UR approval:
Temperatures non-hazardous
fluids (air, water and inert gas)
Ambient Temperature
english
5
INSTALLATION
5.1 Safety instructions
DANGER!
Risk of injury from high pressure in the equipment!
▶ Before loosening the pipes and valves, turn off the pressure and
vent the pipes.
Risk of injury due to electrical shock!
▶ Before reaching into the system, switch off the power supply and
secure to prevent reactivation!
▶ Observe applicable accident prevention and safety regulations for
electrical equipment!
WARNING!
Risk of injury from improper installation!
▶ Installation may be carried out by authorized technicians only and
with the appropriate tools!
Risk of injury from unintentional activation of the system and an
uncontrolled restart!
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
5.4 Manual override (optional Type 6281,
body material brass)
To control the valve manually, the hand lever under the coil must be turned
into the vertical position.
NOTE!
Caution!
▶ Do not overturn hand lever!
▶ When the hand lever is actuated, the valve can no longer be switched
electrically.
Hand lever
english
Type 6213 EV, 6281 EV
Permitted media
2)
-30 ... +120 °C
-30 ... +100 °C
(for 6213 EV DN40)
-30 ... +55 °C
Opened position
Closed position
5