The fans installed on the system has to be electronic (EC).
After an interval of 4 weeks of inactivity, a running period of 3-5 hours is recommended.
Cleaning the finned pack by using the fans is programmable by the controller, and consists of the activation of the fans at a preset
speed and for a preset duration, with inverted direction of rotation. The function starts only with the unit switched on (see controller
manual details).

5 QUALITY OF WATER SUPPLIED TO THE SYSTEM

For Emeritus to function correctly, the water in the system must have the following characteristics in compliance with Directive
98/93/CE concerning drinking water.
Additionalty the followings limit has to be considered:
Conductivity [µS/cm]
Fixed residue [mg/l]
Chlorides [mg/l]
Sulphates [mg/l]
Hardness[°f]
Indicative softener ratio [°f in / °f out]
PH
This primary source water must undergo a softening process before being nebulized to reduce hardness to a value between 4 and
6 °f.
Complete Emeritus system (spray + adiabatic panel): annual use is generally limited to 2000 hours; the value is automatically
balanced by the control system which modulates the water supplied to the exchanger and adiabatic panel depending on the
load and the ambient temperature.
System with adiabatic panel only: no limits are set for annual operation (if non-treated water is used, it is necessary to
increase water quantity by 30%).
System with spray only: annual use limited to 300 hours.
On request, LU-VE can offer a water treatment system. Contact LU-VE for more information.
In the event that water from an osmosis plant is used, a special version of the spray system is constructed in stainless steel at additional
cost. It is also necessary to add the special protective agent LU-WET 82 which is completely biodegradable. In this case, there are no
particular constraints on the maximum annual number of hours of operation of the Spray system.

4 FAN

Limits for Emeritus
800
500
100
50
4 – 6
7
6.5 – 8
21