Component Of Emeritus System; Spray System - LU-VE Emeritus EHVD Serie Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Inox flexible
tubes
The Emeritus system consists of a series of components which are individually illustrated in the following pages:

Spray System

The machine has copper and AISI 304 stainless steel tubes. Water inlet is through a brass threaded pipe union from a 1-1/4" female
adaptor.
The spray ramps are supplied through motorized solenoid valves with 1" connectors with coil supply of 230 VAC.
The control of the solenoid valves, for both supply and automatic draining, is managed directly by the regulation logic.

3 COMPONENT OF EMERITUS SYSTEM

Copper
pipes
The number of spray nozzles for standard plant is 4 per coil module. The
number of spray ramps is 2 per unit side; each ramp, positioned at about the
same height from the base, serves half a coil. In this way, the unit is divided
into four zones which can be wetted independently.
The nebulization nozzles are brass and are supplied at a mains pressure of 2 to
4 barg (maximum operating pressure 7 barg).
Correct maintenance is crucial to ensuring the long-lasting operation of all the
spray products (see action plan of maintenance and intervention reporting).
Nozzles: check periodically that the nozzles function correctly, making sure
that any impurities in the spray unit have not obstructed the water supply
lines.
Water quality
control unit
9