5.3.2
Enabling
EN
5.3.3
Request
72
The machine can be enable by display, remote control (throught dry contact) and modbus
Until the machine will not be enable the compressor cannot start.
The choice of the kind of enabling can e made by display or modbus.
-
DIS: Enabling by display;
-
RC: Enabling by controllo remoto;
-
BMS: Enabling by modbus;
After the enabling on the display will appear the symbol ON.
The machine can follow three differents kind of request, by probes (AUTO), by remote control
(through dry contact) or modbus.
-
AUTO: request by probes. After having set the request on AUTO and set the values of
temperature and humidity desired, the machine will works in order to achieve those set
facing the set and the values read by the probes with priority to the cooling request. In this
mode in case of alarm by the temperature of humidty probe the machine will not
works;
-
RC: request by remote control. After having set the request on RC the machine will works
until one of the dry contacts DEU or COOL are close with priority to the cooling request.
-
BMS: request by modbus. After having set the request on BMS the machine will works until
one of the modbus request for DEU or COOL is on with priority to the cooling request.
M.CS620-00 ITA-ENG-FR 24/05/2021