General guidelines for the installation of the external unit
EN
When the difference in height between compressor and external condeser is more
than 4 m is necessary the installation of a syphon, in the discharge pipe line, to
avoid the flowing back of the refrigerant during the stops. The minimum height of
the syphon must be at least Hmin ≥ 2,5 the pipe diameter.