5.7
EN
76
Version with digital Thermostat
This controller works with 2 probes: Pb1 and Pb3.
When it's powered this controller shows the environment temperature. Pressing the
keys
and
ACTIVATION/DEACTIVATION OF THE TEMPERATURE CONTROLLER:
In order to activate/deactivate this controller press
display the symbol
temperature can be enable or disable. If it's OFF machine will control only Relative.
Humidity.
The temperature set point is 26°C.
MODIFICATION OF THE SET POINT:
In order to modify temperature set point, it's necessary to follow this procedure:
1)
Press contemporary and keep press the keys
display appears the writing "All";
2)
Press keys
3)
Press
4)
Press keys
5)
Press
parameter to the desired value;
6)
Press
Repeat points 4, 5, 6 in order to modify "FA11";
7)
FA11 = FA10 + 0,9°C always. If this rule is not respected machine
doesn't work correctly.
8)
Press
9)
Press keys
10) Press
11) Press keys
12) Press
parameter to the desired value;
ST01 = FA10 + 1°C always. If this rule is not respected machine doesn't
work correctly.
it's possible to see the temperature of the probe Pb1 and Pb3.
appears/disappears. In this way the control of the
until the writing "FA" appears;
and
key to enter "FA" parameters list;
until the writing "FA10" appears;
and
key and then keys
and
key to confirm the new parameter;
key to exit parameter modification;
until the writing "ST" appears;
and
key to enter "ST" parameters list;
until the writing "ST01" appears;
and
key and then keys
and
M.CS620-00 ITA-ENG-FR 24/05/2021
CS
key for 3 seconds. In the
and
and in the
in order to modify "FA10"
in order to modify "ST01"