16.3.1

Diameter of connecting pipes

CS190 TCR
CS300 TCR
CS440 TCR
CS620 TCR
16.3.2

Refrigerant charge for a correct functioning

MODELLO
CS190 TCR
CS300 TCR
CS440 TCR
CS620 TCR
M.CS620-00 ITA-ENG-FR 24/05/2021
It is recommended to install the outdoor unit in consideration of the preferred wind
direction.
The installations are not recommended in figure A, the installations as in figure B
should be preferred.
In order not to compromise the good operation of the unit and its performance,
install the external condenser considering the spaces indicated in figure C for
vertical installations, and in figure D for horizontal installations.
The external condenser must be positioned at a maximum height of 8 meters with
respect to the indoor unit ( see figure E ).
If the external condenser is positioned lower down inside unit , this height must
not exceed 2 meters ( see figure F ).
The maximum length of the pipes between the two units must not exceed 12
The slope of the pipes must be at least 2% to ensure the correct return of the
oil to the compressor. ( see figure G ).
MODEL
For a correct functioning of the unit for each meter of liquid line, add the quantity of
refrigerant indicated in the table below.
Warning: Before loading the unit, check the type of refrigerant indicated on the data plate
MEASURES
D [ mm ]
350
500
500
630
PIPING
GAS LINE [ mm ]
16 X 1
22 X 1
22 X 1
22 X 1
REFRIGERANT TYPE
R410a
R407c
R407c
R407c
L [ mm ]
410
833
833
883
meters.
LIQUID LINE [mm]
12 X 1
12 X 1
12 X 1
12 X 1
QUANTITY [ gr ]
100
100
100
100
91