EN
WARNING
Definition of warning signs:
Indication that a risk of electrical origin exists.
Indication that a risk exists for the machine or its operation.
Directions to be used only by qualified professionals.
Disconnect electrical power before working on the unit!
AREA OF APPLICATION
1
Sanicondens® Pro/Eco is a pump used to lift condensation water from an air conditioning system, a condensation
boiler, dehumidifiers or from refrigeration units. If necessary, insert a neutralisation device (see your boiler manufacturer's
instructions). The use of a neutraliser is mandatory on oil boilers in order to preserve the pump.
The pump starts automatically and has a high level of performance, safety and reliability as long as all the installation and
maintenance instructions mentioned in this manual are strictly followed.
All applications other than those described in this manual are prohibited.
DESCRIPTION
2
2.1 OPERATING PRINCIPLE
Sanicondens® Pro/Eco contains a pump. The tank of the SANICONDENS® Pro/Eco has a built-in a float which
controls the operation of the motor. When the condensate enters the tank, the pump starts up.
Sanicondens® Pro has also a built-in secondary float that can trigger an alarm (audible and/or visual).
2.2 TECHNICAL DATA
Type
Max. vertical pumping
Maximum flow rate
Min. pH
Level ON/OFF
Voltage
Frequency
Current consumption
Power rating
Electrical class
Protection index
2.3 LIST OF PARTS SUPPLIED see pg. 6.
2.4 DIMENSIONS see pg. 9.
2.5 PERFORMANCE CURVES see pg. 11.
2.6 VERTICAL PUMPING/HORIZONTAL PUMPING see pg. 11.
START UP
3
3.1 INSTALLATION
Always install the pump:
– horizontally, using a leveling tool,
– as close as possible to the appliance keeping in mind that the condensate has to drain through gravity into
the pump.
To ensure proper ventilation of the motor, the pump must be free of any obstruction.
The pump can be mounted against a wall using the plastic anchors A and screws B supplied (accessory bag). See fig. 1
and 2.
Check that the Sanicondens® Pro/Eco is leveled: fig. 2.
3.2 HYDRAULIC CONNECTION
Connecting the inlet
The pump has two inlets Ø28 mm that can be used as required (fig 3):
– The left inlet is open.
– The right inlet is protected by a break-off plug. To use the right inlet, first cut out the cut-off plug with a cutter and
remove it.
Drain the condensate water to any of these inlets (fig 4). If necessary, use a rubber flexible adapter C.
CD 10
Sound level
4.5 m
Average operating temperature
380 L/h
Maximum allowable temperature
2.5
56 mm / 4 6 mm
Weight of the unit
220-240 V
Tank volume
50 Hz
Supply cable
0.52 A
Discharge hose
60 W
Alarm cable (2 cores) (Pro)
I
Max. power for the connected boiler
IP20
Wall mounting
14
< 45 dBA
35°C
80°C
S3 15% (1min30 ON/8min30 OFF)
2 kg
2.2 L
1.5 m
5 m, Øint: 10mm
1.5 m
gas: 50 kW / o il: 30 kW
Yes