Fine Adjustment; Simulation Mode; Spare Parts; Accessories - Camille Bauer KINAX WT 711 Mode D'emploi

Convertisseur de mesure pour angle de rotation
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Take off the plastic cover.
Undo the gland nut and remove the pinch ring and seal from
the gland opening. Place these parts over the cable in the
correct order and pass the end of the cable through the gland
hole into the housing of the transmitter.
Strip the insulation from a suitable length of the leads and
connect them to the terminals (5) according to the wiring
diagram (Fig. 9). Attach the leads to the support (6) with a
cable strap.
Then fi l the gland seal, pinch ring and nut. Tighten the gland
nut and replace the cover.
R
ext
+
– +
H
Fig. 9. Connection diagram.

9. Fine adjustment

The analog output can be fi nely adjusted using the 2W2
confi guration software. Select the menu item "Adjustment"
under "SERVICE". In the "Analog output" window, the zero
position and the end value can now be adjusted.
Procedure:
1. Put the transmitter into operation and connect the pro-
gramming device according to Fig. 6 (AUX switch on the
PK 610 on the OFF position).
2. Place the measuring device in the zero position, i.e. in
the position, in which the KINAX WT 711 should output 4
mA. Adjust with the "ZERO" virtual knob until the output
is correct.
3. Place the measuring object in the end position, i.e. in the
position, in which the KINAX WT 711 should output 20 mA.
Adjust with the virtual knob "Span" until the output signal
is correct.
4. Close the adjustment with the "Done" button.
The adjusting range of the zero position and span is 5%.
If this range is not suffi cient, the span can be adapted by
changing the mechanical characteristics (increase/decrease
the measuring span).
H = DC power supply
H = 12...33 V
resp. H = 12...30 V
with Ex version
R
= External resistance
ext
If required, the direction of rotation can be reversed using
the confi guration software.

10. Simulation mode

The 2W2 confi guration software supports the operation of
the KINAX WT 711 in simulation mode. The simulation of the
measured value allows the subsequent chain of devices to
be tested during the installation phase.
Procedure:
1. Select the "Simulation" menu item under "Service" in the
confi guration software.
2. The window displays the device confi guration. After the
entry of the required angle, the analog output is set in
accordance with the device confi guration.

11. Accessories

Description
Programming cable PK 610
DSUB 9p F
1 meter
Ancillary cable
1.5 meter
Confi guration software 2W2
on CD (download free of charge under
http://www.camillebauer.com)

12. Maintenance

The device is maintenance free.
Order
No.
137 887
Interface
141 440
146 557
17