Mounting and securing
6.4
Adjusting door closer
1
Adjustment closer size
2
Adjustment closing speed
Adjust closing force (1) to match the door width.
X
Set closing speed (2).
X
à In accordance with EN directive for fire protection doors, the door closer must be
set at least to size EN 3.
à Adjustment of closing speed in accordance with EN 1154 (closing time approx. 5 s
from 90° open position).
à Smooth-moving door must be completely closed by the closer!
à In combination with guide rails, the door closer size is between EN 1 and EN 3.
6.5
Mounting cover panel
CAUTION!
Do not pinch cable.
X
Attach protective cap in such a way that the smoke switch opening is concealed in the cover to protect
X
the interior of the system from contamination.
Protective cap must be removed during commissioning of the hold-open device.
Clip on cover panel (1.).
X
Clip on protective cap (2.).
X
Clip on cover cap (3.).
X
Bring company logo into readable position and press in flush with the surface (4.).
X
IMPORTANT
Following the guideline for hold-open systems by the DIBt (German Institution for Construction Technology) the
installation of a circuit breaker is compulsory, if door closers with free-swing function are used.
GB 8
Closer size
1
2
3
4
5
6
Specifications EN 1-6 are applicable only for use with
rods.
TS 4000 R
Fig.: 6.4.1
Leaf width a [mm]
till 750
750 - 850
850 - 950
950 - 1100
1100 - 1250
1250 - 1400
Sec
Fig.: 6.5.1