Mounting and securing
Mark out and drill fixing holes for door closer and guide rail using fitting template or cut M5 thread if necessary.
X
Drill additional hole (A) for 230V power supply.
X
If necessary, make opening for additional connections (B).
X
IMPORTANT:
To guarantee correct functioning of the smoke switch, GEZE recommends
that the distance between the upper edge of the door closer and the ceiling
be at least 10 mm!
6. 1 .2
Mount door closer and rod
For concealed connection, route 230 V mains cable into the terminal area (see section „Mains connection") (1.).
X
Mount door closer (2.).
X
DIN left
TS 4000 R BG
Position lower part of rod and screw down (2.) (tigh-
X
tening torque: 14 Nm, closing angle approx 80°).
Screw lower part of rod assembly to the door
X
(tightening torque: 14 Nm) (3.).
latching action setting
GB 4
DIN right
with latching action
TS 4000 RFS BG
Turn driver plate into the correct position (1.).
X
Position lower part of rod and screw down (2.) (tigh-
X
tening torque: 14 Nm, closing angle approx 80°).
Screw lower part of rod assembly to the door
X
(tightening torque: 14 Nm) (3.).
without latching action
TS 4000 R
>10 mm
Fig.: 6.1.1.2
Fig.: 6.1.2.1
Fig.: 6.1.2.2