GEZE TS 4000 R KM BG Instructions De Montage page 17

Publicité

Les langues disponibles

Les langues disponibles

TS 4000 R
Insert end caps (1) in sliding rail.
X
Fasten guide rail with screws (2).
X
Open adjustment valve (closing speed) (3) again.
X
6.3
Mains connection
DANGER!
Hazard of electric shock!
Electric wiring must only be carried out by professional electricians.
Operating voltage: 230 V AC +10 % / –15 %.
Interrupt power supply!
X
The GEZE hold-open devices FA GC are appliances of the protection class I
The 230 V supply line is double insulated (with cable jacket) to be inserted at least 8 mm into the terminal area.
Appliances of the protection class I are connected with a three-core cable NYM-J 3 x 1.5.
Use cable protection for the 230 V cable when leading through plaster.
Insert the 230 V cable/cable for additional connections protruding from the wall through the
respective openings of the smoke switch housing.
Fuse the on-site mains connection with a B10 fuse.
X
Remove cover of cable connection (1.).
X
Shorten 230 V power supply cable to approx. 80 mm (2.).
X
Place 230 V power supply cable on site on the terminal and connect (3.).
X
Fit cover of cable connection (4.).
X
Mounting and securing
Fig.: 6.2.2.3
.
Fig.: 6.3.1
GB 7