SL24.W
Motor stop approach force
reduction distance
Indicates the distance from the
mechanical stop starting from
which the motor force is reduced
by half (used to adjust the impact
of the leaf on the mechanical
stop).
T15
This happens only when the con-
trol panel works with encoder and
proximity limit switch or without
limit switch.
Force reduction off
Minimum force reduction distance
Maximum force reduction distance
Easy release
Disengagement time after
manoeuvre to reduce the motor
pressure on the mechanical stop
T17
(adjustable at intervals of 100 ms)
No disengagement
100 ms (minimum disengaging)
500 ms (maximum disengaging)
Normal motor speed when
opening
T24
minimum speed
maximum speed
Normal motor speed when
closing
T26
minimum speed
maximum speed
Motor slowdown speed when
opening
T28
minimum speed
maximum speed
Motor slowdown speed when
closing
T30
minimum speed
maximum speed
Motor slowdown distance when
opening
% of travel or total work time done
T32
at slowdown speed
No slowdown
Slowdown for the whole distance
Motor slowdown distance when
closing
% of travel or total work time done
T34
at slowdown speed
No slowdown
Slowdown for the whole distance
Motor acceleration time when
opening
Time during which the motor
accelerates to reach the normal
opening speed (adjustable at inter-
T36
vals of 0.1 s)
(OFF)
Maximum acceleration (0 s to
reach normal speed)
Minimum acceleration (2.0 s to
reach normal speed)
Motor acceleration time when
closing
OFF
Time during which the motor ac-
T38
10
celerates to reach the normal clos-
100
ing speed (adjustable at intervals
of 0.1 s)
Maximum acceleration (0 s to
(OFF)
reach normal speed)
T38
Minimum acceleration (2.0 s to
reach normal speed)
OFF
Motor deceleration ramp
10
Deceleration ramp between nor-
mal motor speed and slowdown
50
T40
speed
90
Steep ramp (maximum deceleration)
Low ramp (minimum deceleration)
1
Auxiliary output configuration
100
Sub
Description
90
menu
Terminal A1 output type
1
Output off
100
Gate open warning light (SCA)
Operation as per SCA parameter
30
setting
1
Auxiliary Radio output (RAU)
Operation as per RAU parameter
100
setting
(30)
Courtesy light (LCO)
On during leaf movement and for
1
the amount of time after the leaf
100
stopping set in parameter LCO
A1
Zone light (LZO)
On during leaf movement
(20)
Gate left open (OAB)
On if the gate remains open for a
0
time longer than that defined by
the open gate alarm logic (L16)
100
Maintenance (MAN)
Output off when the number of
(20)
maintenance signalling manoeu-
vres (MNPS) is reached in the
diagnostics section
0
100
EN
(0.5)
0
2.0
(0.5)
0
2.0
(30)
0
100
Values
(default)
(1)
OFF
1
2
3
4
5
6
17