ENGLISH
VIII.5.c. TABLE
INPUT REGISTER
Function
System status
External temperature
Operating temperature of the
blower fan
Operating temperature of the
recovery fan
Supply temperature
Extraction temperature
Fresh air pressure
Recovery air pressure
CO2
Defrost temperature
Humidity
Defrost heater temperature
Analogue output
Analogue output
Analogue output
Analogue output
Analogue output
Description
Modbus :
0= stop
1= startup
2= low speed startup
3= maximum speed startup
4= normal speed startup
5= in operation
8= o CO2 operation
9= Night cooling
11= shutting down
BACNET :
1= stop
2= startup
3= lo speed startup
4= maximum speed startup
5= normal speed startup
6= in operation
9= CO2 operation
10= Night cooling
12= shutting down
LOBBY EC
LOBBY EC
DIVA
0-10 V heating (WATER COIL)
0-10 V Heat exchanger
0-10 V Heat exchanger
0-10 V Supply
0-10V Recovery
Exo type Modbus
address
X
3
R
1
R
4
R
5
R
7
R
9
R
13
R
14
R
17
R
21
R
23
R
25
R
54
R
55
R
56
R
57
R
58
Bacnet
Default
address
value
MSV,40003
AV,40001
AV,40004
AV,40005
AV,40007
AV,40009
AV,40013
AV,40014
AV,40017
AV,40021
AV,40023
AV,40025
51