V.4.c. Modifying the temperature setpoint

[(8) section V.3.b]
Access : Temperature control
The setting is based on the temperature of :
• the supply with external compensation (standard setting). In other words, the setpoint for the temperature changes
according to the external temperature. This rule is defined in order to comply with RT 2012
• Recovery.
V.4.d. Forced shutdown of control unit or forced LS or HS operation on the remote control
[(7)section V.3.a]
Access : Operating mode/Operating mode
It is possible to stop (7) (shut down) the system via the CORRIGO command or execute a forced LS (7) (manual speed
1/2) or HS (7) run (manual speed 1/1). As standard, the system operates in Automatic mode controlled by the timers
(7) (Auto)
An alarm will be generated the moment the system is taken out of Auto mode. Note that the manual speed 1/1
!
and manual speed 1/2 modes are used exclusively for activation and repairs. Any other setting will cause a
system malfunction.

V.4.e. Language selection

[(10) section V.3]
Access : Initial screen/Language selection

V.5. Intermediate settings (function level)

In order to modify the setting type, the Night Cooling parameters and CO 2 setpoint you need access to the configuration
menu at system level. This requires authorization to access the "Function" level. The procedure is as follows.
Access rights
Enter the code 2222 using the arrow keys then press OK to confirm. Press the left arrow key twice to access the menus.
If you make a mistake, press C twice and repeat the operation.

V.5.a. Configuration menu with function level access

Configuration
1. Selection of the setting type (see section V.5.b.1)
2. Modification of Night Cooling parameters (see section V.5.b.2)
3. Modification of CO 2 setpoints (DIVA and QUATTRO only) (see section V.5.b.3)
Enter
Control function
Ventilation
CO2/VO Ctrl
Enter the password 2222
For the required authorization level :
Current lev. : FUNCTION
Control function
Mode :
Supply + ext. comp (1)
Ventilation active : YES (2)
Ext. temperature activation : 22°C (2)
Night external T°
High 18°C (2)
Low 10°C (2)
Mini ambient temp : 18°C (2)
Speed : 85%
CO2/COV ctrl active :
Run timer yes
Type Fan
Speed 1/2 : 800 ppm (3)
Speed 1/1 : 1000 ppm (3)
Diff : 160 ppm
33