V.3.A. Operation Mode Menu - Vortice VORT NRG 600 EC Manuel D'utilisation Et De Mise En Marche

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ENGLISH

V.3.a. Operation Mode menu

Operating mode
(7) Run/Stop setting (see section V.4.d)
Operating mode
...
Alarm report
...
Inputs/Outputs
Operating mode
Auto (7)
Operating period
AS Fan: 00.0
H
Operating period
00.0
H
Alarm log
(Use the down arrow to scroll through the log)
AI
AI1: AS T° (supply air)
Analogue inputs
AI2: Ext T°(external)
AI3: Defrost T°.
AI4: AR T° (recovery air)
DI1: Al Filter1
DI
DI2: Overheating
Digital inputs
or Ext Ant. Prot
DI3: Forced run 1/2
DI4: Forced run 1/1
DI5: Ext stop
UI
UAI1: Sup. circuit T° (defrost coil)
Universal inputs
UAI2: AS press (LOBBY)
UAI3: AR press (LOBBY)
UAI4: CO2 (DIVA)
UDI2: VAS run
UDI3: VAR run
AO1: Y1 Heating
AO2: Y2 heat exchanger or M3V
AO
AO3: Y3 Cooling
Analogue outputs
AO4: VAS Ctrl
AO5: VAR Ctrl
DO1: VAS V freq.
DO2: VAR V. freq
DO3: Electric battery heater or heating
pump
DO4: Cooling pump
DO5: Alarm total
DO6: Sup. control. (DBE)
DO7: Ventilation activated (LOBBY)
29