Vortice VORT NRG 600 EC Manuel D'utilisation Et De Mise En Marche page 40

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ENGLISH
Title
Description
35
Manual
Operation in
manual mode
from
...in manual
Some functions
36
mode
have switched to
to
manual mode.
44
48
Low charge
Internal battery
error
49
AS temp
Check value on
sensor error
Ext Al1
50
AR temp
Check value on
sensor error
Ext Al3
55
VAS pressure
Check value on
sensor error
Ext UAI1
56
VAR pressure
Check value on
sensor error
Ext UAI2
59
CO2 sensor
Check value on
error
Ext AI 4
85
...in manual
Some functions
mode
have switched to
manual mode.
86
Carry out the
Periodic
servicing
inspection
operation
87
...in manual
Some functions
mode
have switched to
manual mode.
VI.3. Cancelling the "Servicing required" alarm
For these parameter settings, it is necessary to access the setting menu. This requires authorization to access the
"Function" level.
The procedure is as follows.
Access rights
Enter the code 2222 using the arrow keys then press OK to confirm. Press the left arrow key twice to access the menus.
If you make a mistake, press C twice and repeat the operation.
Settings
A service alarm is generated every 6 months. Enter YES to reset the counter.
40
Type
Time Cause
C
5 s
Fault for information only (the system has switched to shutdown in PV
or to PG directly on the display (see (7) section V.3.a)
C
5 s
In the Manual/Auto menu all options should be set to Auto.
A
5 s
The internal battery of the CORRIGO is faulty.
Change the battery so as not lose the program.
See section VII.2
A
5 s
The SSG external temperature sensor is out of service
The SSG external temperature sensor is wired
incorrectly (see section V.3.a)
A
5 s
The SRG external temperature sensor is out of service
The SRG external temperature sensor is wired
incorrectly (see section V.3.a)
A
5 s
The 0-10 V signal is inverted
The fresh air pressure sender is short-circuited
A
5 s
The 0-10 V signal is inverted
The recovery air pressure sender is short-circuited
A
5 s
The 0-10 V signal is inverted
The CO2 pressure sender is short-circuited
A
5 s
In the Manual/Auto menu all options should be set to Auto.
C
5 s
See section VI.3
C
5 s
In the Manual/Auto menu all options should be set to Auto.
Enter
RAZ filter counter
Enter the password 2222
For the required authorization level :
Current lev. : FUNCTION
Filter alarms
Reset the
Timer : YES

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vort nrg 800 ecVort nrg 1500 ecVort nrg 2000 ecVort nrg 2500 ecVort nrg 600 ec ehVort nrg 800 ec eh ... Afficher tout

Table des Matières