ENGLISH
V.6.a. Configuration menu with admin level access
Configuration
1 and 2 Activation of MODBUS RS485 and settings (see section V.8)
3 and 4 Activation of BACNET MSTP and settings (see section V.8)
5 and 6 ITCP/IP settings (see section V.8)
7 and 8 Activation of BACNET IP and settings (see section V.8)
9 Repeater addressing (see section V.8)
V.7. Modification of function parameters
V.7.a. MODBUS
A simplified MODBUS is presented at the end of the operating and commissioning instruction manual.
Access: Configuration/Communication
MODBUS TCP/IP is activated as standard in DHCP. It is possible to know the DHCP address or set the fixed IP [(5)(6)
section V.6], Modbus port= 502/Device ID = 255
It is necessary to activate the MODBUS RS 485 [(1) section V.6]. Possibility to set speed, parity, stop bits, etc. [(2) section
V.6].
Modbus type
1 = Coil status register (Modbus function 1, 5 and 15)
2 = Input status register (Modbus function 2)
3 = Company register (Modbus function 3, 6 and 16)
4 = Input register (Modbus function 4)
Communication
System
Modbus slave
Port 1:
communication
Slave
Port 1
Active (1)
Bacnet
MSTP
communication Port
1
Active (3)
DHCP: YES (5)
TCP/IP
Current Ip:
Bacnet IP
communication
Active (7)
Addresses
PLA: 254 (9)
ELA: 254 (9)
Modbus address: 1 (2)
Speed: 9600 Bps (2)
2 stop bits: Yes (2)
Parity No (2)
Device name: - (4)
Mac: 0 (4)
Low device ID: 2640 (4)
High device ID: 0 (4) (x10000)
Speed: 9,600 Bps (4)
Master max ad.: 127 (4)
IP - (6)
Subnet Mask - (6)
Subnet Mask - (6)
Gateway - (6)
Device name: - (8)
BBMD address: 0 (8)
Low device ID: 2640 (8)
High device ID: 0 (8)
(x10000)
UDP low port N° 7808(8)
UDP high port N° 4(8)
(x10000)
35