Device ID: The ID of a device, used to identify it on the BACnet. This number must not be duplicated anywhere else on
the BACnet and therefore must be unique. To set an ID value of 34600, the low number must be set to 4600 and the high
number to 3
For more information, refer to the CORRIGO images at http://www.regin.se

V.8.a.4. LON communication (if CORRIGO with LON option)

Set the LON function as follows:
In the menu Configuration/Communication/Function port 2 = activate port 2 in the extension unit.
Go to the right and activate the extension unit. 1 in CORRIGO E28 LON
The button for the PIN service is located on the rear of the controller.
The communication table is located at http://www.regincontrols.com

V.8.a.5. Activation of fire protection function

Setting the input parameters
Access: Configuration/Input Output/DI/ DI8
Declare input DI8 as "Fire Al" "NO"
Definition of function parameters
Access: Configuration/Fire protection function
Select the required operating mode to be activated when the fire protection function is activated
"Shutdown": Total shutdown of the unit
"Continuous operation" Startup or maintenance of unit operation in HS mode.
The fire protection function will have priority over all other alarms.
"Normal operation": the unit will continue to operate within the parameters selected on site (stop/LS/HS)
"Exhaust fan only": Start or maintain exhaust fan operation in HS mode (the recovery fan is stopped)
"Recovery fan only": Start or maintain recovery fan operation in HS mode (the exhaust fan is stopped)
Alarm setting
Access: Configuration/alarm configuration
Enter alarm number "10", go to the right and enter in priority "C alarm C" "Active"

V.8.a.6. Activation of the dehumidification function

Input settings
Access: Configuration/Input Output/UI/ UI4
Declare input UI4 "Ambient humidity"
Function setting
Access: Configuration/Humidity control
"Select dehumidification"
Reference value setting
Access: Humidity control
Enter the desired setpoint
37