3.9. aLaRM On tHE LCD SCREEn
the Rt9s can indicate several alarms:
►
MAINTENANCE
►
CATCHING UP PULSES
►
WAITING FOR PULSES
►
ERROR: PULSE SC
►
ERROR: PULSE OC
►
Maintenance :
For the procedure to follow, please contact our technical department (contact details on
the back of this document).
Catching up pulses:
►
As the pulse receiving clocks are running late, the RT9s sends pulses until the clocks
are set to the exact time.
►
waiting for pulses:
As the pulse receiving clocks are running fast, the RT9s will wait for the clocks to be set
to the exact time before sending a new pulse.
►
Error: Pulse SC:
This alarm indicates that the pulse line is short-circuited.
Check the state of the pulse line before restarting the pulses via the LCD screen (see
Section 3.7. puLSe ouTpuT) or via the Web interface (see Section 4.6. TiMe inpuTS
/ ouTpuTS paragraph 4.6.2 Detailed description of time outputs).
►
Error: Pulse OC:
This alarm indicates that the pulse line is in open circuit.
Check the state of the pulse line before restarting the pulses via the LCD screen (see
Section 3.7 puLSe ouTpuT) or via the Web interface (see Section 4.6 TiMe inpuTS
/ ouTpuTS paragraph 4.6.2 Detailed description of time outputs).
.