Annex

5.1

Technical data

5.1.1

Digital inputs

Quantity
Per optional board
(expansion slots 1 to 3)
Input signal
Current
5.1.2

Digital outputs

Quantity
Standard version
Per optional board
(expansion slots 1 to 3)
Output signal
Current per output
Total current of all outputs
5.1.3

Electrical data

Voltage supply
Connection
Voltage
Residual ripple
Current consumption
Power consumption
External voltage supply
Connection
Voltage
Residual ripple
Admissible current
Inputs and outputs (terminals 1 to 32) and ex-
ternal voltage supply (terminals GND and
+24 V)
Max. 15
5
DC 0/24 V
(PLC level; logical "0" = -3 to +5 V; logical "1" = 15 to 30 V)
Max. 5 mA per input
Max. 32
17
5
DC 0/24 V (depending on external voltage supply)
Max. 500 mA, short-circuit proof
Max. 16 A
Observe electrical data for the external voltage supply!
For module electronics
Lateral (supply via central processing unit or router module 705042)
DC 24 V +25/-20 % SELV
5 %
Max. 123 mA (module electronics only; at DC 19.2 V)
Max. 3 W (module electronics only)
For digital inputs/outputs
At the front (removable terminal strip, 2-pole with Push In technology)
DC 24 V +25/-20 % SELV
5 %
Depending on the ambient temperature and mounting distance
above the module
At 70 mm distance:
55 °C: max. 13.0 A
54 °C: max. 13.5 A
51 °C: max. 14.0 A
48 °C: max. 14.5 A
45 °C: max. 15.0 A
42 °C: max. 15.5 A
≤ 40 °C: max. 16.0 A
At the front (removable terminal strips with Push In technology)
At 35 mm distance:
55 °C: max. 10.0 A