4
Annex
4.1
Technical data
4.1.1
Interfaces
System bus (output, lateral)
Description
Type
Number
Application
System bus (input, front side)
Description
Type
Number
Connecting cable
Application
System bus (output, front side)
Description
Type
Number
Connecting cable
Application
4.1.2
Electrical data
Voltage supply
Connection
Voltage
Residual ripple
Current consumption
Power consumption
Conductor cross section on terminals GND
and +24 V
Wire or stranded wire without ferrule
Stranded wire with ferrule
2 × stranded wire with twin ferrule
with plastic collar
Stripping length on terminals GND and +24 V 10 mm
Electrical safety
Protection rating
Electromagnetic compatibility
Interference emission
Interference immunity
None (side plug connector)
System specific
1
Connection to an input/output module
Bus In
RJ45
1
Network cable (patch or crossover cable), at least CAT5 (S/FTP)
Connection with a router module 705041 (on the same DIN rail as the
central processing unit) or 705042 (on separate DIN rail)
Bus Out1, Bus Out2
RJ45
2
Network cable (patch or crossover cable), at least CAT5 (S/FTP)
Connection with router modules of the JUMO variTRON automation
system
At the front (removable terminal strip, 2-pole with Push In technology)
DC 24 V +25/-20 % SELV
5 %
100 mA (at DC 19.2 V)
Current consumption of lined-up modules also has to be considered!
2 W
2
Min. 1.5 mm
, max. 2.5 mm
2
Min. 1.5 mm
, max. 2.5 mm
2
1.5 mm
According to DIN EN 61010-1
Overvoltage category III, pollution degree 2
III
Acc. to DIN EN 61326-1
Class A – only for industrial use –
Industrial requirement
2
2
4 Annex
25