Definition Of Explosion-Proof Protection; Equipotential Bonding - FLUX F 550 Notice D'instructions

Masquer les pouces Voir aussi pour F 550:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.1.1

Definition of explosion-proof protection:

Category 1 (ZONE 0): The external part of the pump between the pump suction end
and its outlet connection.
Category 2 (ZONE 1): The external part of the pump between its outlet and the connec-
tion part to the drive motor as well as the internal part of the pump. (During pumping,
the internal part of the pump will always be filled by the liquid).
4.2

Equipotential bonding

If the motors are operated together with the pump, comprehensive, clear equipotential
bonding is essential (earthing, Fig.1)
Pump/motor connection
Bearing flange or planetary
gear
2
Pump
Suction end
of the pump
Category 1 (Zone 0)
Category 2 (Zone 1): ambiance close to category 1
Fig. 2: Earthing in hazardous locations
> Connect the earth continuity conductor (earth wire) (1) to the designated screw on
the explosion-proof motor.
> Connect the earth continuity conductor (earth wire) (2) to the designated screw on
the pump. If the connection between the motor and pump already provides a con-
ductive path (for pumps for flammable liquids), one of the equipotential bonding
conductors may be dispensed with.
> The containers should be grounded separately (3), if they are not already grounded
by the mode of installation.
> Only use hose lines (4) with conductive hose unions (see TRbF 50 Annex B.
6
(R < 10
Ω). This will provide a conductive path for the pump, hoses and fittings.
> Only use an explosion-proof plug or an explosion-proof terminal box when making
connections to the mains (5).
> Remove paint and dirt from all connection points of equipotential bonding conduc-
tors and transition points of the containers to the electrically conductive base ground
to ensure good conductivity.
Original Operating Instructions High Viscosity Liquid Pump F 550 and Sanitary Pump F 560
5
Drive motor
1
Pump outlet
4
Conductive hose
6
R < 10
Ω
3
3
49/116

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

F 560

Table des Matières