Fault finding guide
Important!
If the dehumidifier is not functioning correctly, shut it down immediately!
Fault finding
Use this table to localize and solve a possible problem or fault:
More help
If you cannot find the reason for the fault, switch off the unit immediately in order to
prevent further damage. Contact a service technician or a Dantherm representative.
35
Fault
The dehumidifier does not
work
No light in the LEDs on the
display
The dehumidifier does not
work
The triangle lights up con-
stantly in red
The compressor does not
work
The lighting on the display
is light up in green
Solution
Check the external fuses
Check the power supply to the unit
Reset pressostat and thermal relay
If the dehumidifier does not work after several reset-
tings of HP pressostat and thermal relay:
Check that the room temperature is between 20
and 38°C
Check that the fan is running
Check that the inlet and outlet air duct are free
from obstruction and whether the filter is clean
Check the room or duct hygrostat by setting it to
a low relative humidity (10-20%)
If the unit still does not start, check the room or duct
hygrostat for defects.