Type 3: Configuration errors in the INTERBUS Air LINE station
No. Meaning
1
The AirLINE module is not released
for operation at the field bus coupler.
2
The linear code of the AirLINE inline
module corresponds to a length of 0
byte.
3
The linear code of the AirLINE inline
module corresponds to a length of
more than 64 bytes.
4
INTERBUS Loop-1 modules are not
released for operation at the field bus
coupler.
5
The sum of the process data in the
INTERBUS and INTERBUS Loop-2
is greater than 250 bytes.
6
More than 64 INTERBUS inline and
INTERBUS Loop-2 modules are
inserted.
7
The sum of the process data for the
inputs and outputs for the Profibus is
greater than 192 bytes.
Type 8644
All manuals and user guides at all-guides.com
Cause and remedy
An AirLINE inline module is not released for operation at
the IL PB BK. Remove the module from the station.
The linear code of the AirLINE inline module corresponds
to al length of 0 byte. Check the module and if necessary
remove it from your configuration.
The linear code of the AirLINE module is too long.
Remove the module from your configuration.
The AirLINE station contains an INTERBUS Loop-1
module. Remove the module from the station and
repalced by an INTERBUS Loop-2 module.
The sum of the process data for the INTERBUS local bus
is greater than 250 bytes. Check the number of process
data and reduce the number of modules in the station.
Check whether more than 64 INTERBUS inline and
INTERBUS Loop-2 modules are present in the station
and reduce the number of modules.
The sum of the process data for the inputs and outputs
for the AirLINE station is greater than 192 bytes. Remove
modules from the station.