M
T
AINTENANCE AND
ROUBLESHOOTING
Type 2: Configuration errors on the PROFIBUS (CHK_CFG-telegram)
No. Meaning
1
Fewer AirLINE modules were
configured than are physically
present.
2
More AirLINE modules were
configured than are physically
present.
3
The first byte of the special identifier
format of the AirLINE module is
faulty.
4
Too few bytes of the special identifier
format for the last AirLINE module
were configured.
5
The sum of the process data
configured is greater than 192 bytes.
6
The ID code in the configuration
does not agree with that of the
AirLINE module.
7
The linear code in the configuration
does not agree with that of the
AirLINE module.
8
The number of manufacturer-specific
data is not equal to 2, 3 or a multiple
of 2.
9
Too few output bytes configured for
the AirLINE module.
10
Too few input bytes configured for the
AirLINE module.
11
For the Profibus configuration, more
than 244 bytes are required.
MT 4
All manuals and user guides at all-guides.com
Cause and remedy
Fewer AirLINE modules were configured than are
present in the station. Add the modules to the
configuration.
More AirLINE modules were configured than are present
in the station. Delete the surplus modules from the
configuration.
The first byte of the special identifier format of the
AirLINE module is, for example, faulty because of a
space or a normal identifier. Locate the error exactly
using the device-specific diagnosis in your control
system.
The special identifier format for the last AirLINE module
is incomplete. Check the identifier format.
The sum of the process data configured for inputs and
outputs of the AirLINE station is greater than 192 bytes.
Locate the error exactly using the device-specific
diagnosis in your control system. Collect several AirLINE
modules together in the configuration in order that the
process data are compressed (fewer blank bits).
The ID code of the AirLINE module configured does not
agree with the ID code of the module in the station.
Locate the error exactly using the device-specific
diagnosis in your control system. Check the configuration
in the hardware configurator.
The linear code of the AirLINE module configured does
not agree with the linear code of the module in the
station. Locate the error exactly using the device-specific
diagnosis in your control system. Check the configuration
in the hardware configurator.
The number of manufacturer-specific data of the special
identifier format for the last AirLINE module is faulty. The
number is 2, 3 or a mulitple of 2. Locate the error exactly
using the device-specific diagnosis in your control
system.
Within the identifier format, too few output process data
for the AirLINE module were configured. Locate the error
exactly using the device-specific diagnosis in your control
system.
Within the identifier format, too few input process data for
the AirLINE module were configured. Locate the error
exactly using the device-specific diagnosis in your control
system.
If necessary, place identical modules that are smaller
than 5 bit in a row next to each other.
Operating Instructions No. 804 104