Using the Communications Port
The PanelView 300 Micro terminal is available in 2 versions.
Catalog Number
2711-M3A18L1
2711-M3A19L1
Both versions have an identical RS-232 communications port with a MicroLogix
8-pin mini-DIN style connector. The only difference is the protocol firmware
(DF1 or DH485) pre-loaded at the factory. Both versions of the protocol
firmware are supplied with the PanelBuilder32 software. You can change the
protocol by downloading the firmware to the terminal using the Windows
PanelView MotherBoard Firmware Download Utility (WinMBFWDL) utility.
This utility is included with the PanelBuilder32 software.
The following table lists the communication parameters supported by each of the
protocols on the RS-232 communications port.
Communication Link
RS-232 or DH-485 Link Point-to-Point
Baud Rate:
Maximum Distance
DF1 - Full Duplex Communication
Baud Rate
Maximum Distance
Communication Port
RS-232
RS-232
RS-232
8-pin mini-DIN
connector
Port is used for both
communications with a controller
and to transfer application files.
Communication Parameters
1200, 2400, 9600, 19.2K Baud
6.1 meters (20 feet)
1200, 2400, 4800, 9600, 19.2K Baud
15.24 meters (50 feet)
PanelView 300 Micro Terminal
Communication Protocol
DF1
DH485
2
5
4
8
7
Pin #
Signal
1
NC (No Connection)
2
GND
3
RTS
4
RXD
5
NC (No Connection)
6
CTS
7
TXD
8
GND
13
1
3
6
41061-156-01(A)