WIRING
All wiring harnesses used must be routed seperate from any mains or non-class 2
voltage cables or must be rated for the mains voltage and suitable protection and
routing means must be used in accordance with national and local codes.
DOOR TYPE
single
simultaneous
pair
dual egress
Power
1
Most doors require the use of the LZR-microscan Power Supply.
For information on powering directly from door control see Tech Bulletin #53.
1a
If using door control power,
connect Power Supply
Harness to door control.
3
Plug Power Supply or Power
Supply Harness into hub port
labeled Power.
Monitoring
LZR-microscan hub/sensors are intended to be monitored by door system for proper operation
(see Tech Bulletin #53). If door control does not utilizing monitoring, do not use monitoring
wires.
Page 8 of 12
Page 8 of 12
always use DOOR CONTROL A hub port
from header cover side, left door uses DOOR CONTROL A hub port and
right door uses DOOR CONTROL B hub port
from header cover side, whichever door is pushed (right door) during Teach
In process uses DOOR CONTROL B hub port
1b
If using BEA provided power
supply, cut plug off of harness
and strip wires
NOTES:
1: LZR-microscan hub/sensors must be powered by a UL Class 2
power supply limited to 15 W.
2: If a NEMA 5-15R outlet is not available in door header, cut off
NEMA 5-15P plug and wire nut to 110V AC observing polarity and
grounding. By cutting off plug, system changes from UL Listed to
UL recognized.
IMPORTANT:
HUB PORT
Power
Supply
.
2
2b
Wire nut input of power
supply to 110V power source.
75.5753.10 LZR-MICROSCAN 20170310