SPECIFICATIONS
Environmental
Ambient Operating Temp
Ambient Storage Temp
Relative Humidity
Motor Protection
Overload Current Setting Range
Overload Trip Class
Overload Service Factor
Under Power (Dry Run)
Over Power
Under Voltage
Over Voltage
Voltage Phase Loss
Ground Fault (UL 1053 Certified)
Cycle Fault
SMARTSTART™ Protection
Current Phase Unbalance
Locked Rotor/Stall
Out of Calibration
Max Time to Start
54
-5 ° F to 140 °F (-20 °C to 60 °C)
-5 ° F to 158 °F (-20 °C to 70 °C)
5% to 95% non-condensing
Adjustment/Description
1-135A, up to 1000A with external CTs
Adjustable: 5-30
Adjustable: 1.00-2.00
On/Off/Alarm, adjustable: 1-99% of nominal
On/Off/Alarm, adjustable: 101-200% of nominal
On/Off/Alarm, adjustable: 80-99% of nominal
On/Off/Alarm, adjustable: 101-125% of nominal
Always On
On/Off/Alarm, adjustable: 1-10 Amps
On/Off, start limit adjustable: 2-100
Adjustment/Description
On/Off, adjustable: 1-50%
On/Off, trips if current exceeds 300% max amps
for 0.5 second
On/Off, trips after 10 seconds if max amps setting
is incorrect
On/Off, regardless of max amps or I
always trip at start if starting current is outside of
an acceptable range and still decreasing after ten
seconds.
Default Setting
1.0 A
10 - SMS, 5, SMS-RV
1.15
On/65%
On/125%
On/90%
On/110%
On/Trips if below 60VAC
On/1A
On
Default Setting
On / 5%
On
Off
2
T trip curve,
Off

Publicité