INSTALLATION AND SETUP
Electrical Installation
Branch Circuit Protection
Some SubMonitor Connect models provide branch circuit protection, varying by SKU and motor voltage. For
branch circuit protection ratings, refer to
Short circuit rating is 600 VAC, 200,000 A.
Special Consideration for Electromagnetic Compatibility (EMC)
SubMonitor Connect conforms to EN60947-4-1 (for EMC). Some installations might need additional EMC
filtering.

Terminal Connections

NOTE:
The connectors shown are model-dependent. Your device might not have all the connectors shown.
Control terminals accept 26-14 AWG wire tightened to a torque of 3.5 in-lb (4 kg-cm). Strip insulation from
wires to a length of 5/16" (8 mm).
1.
Voltage Inputs – (L1, L2, and L3). These connections provide external power to the SubMonitor Connect
and must match the phase relationship with phase A, B, and C respectively. L1, L2, and L3 come from
the output of the power disconnect or from the line side of the contactor, before the cables to the
motor pass through the SubMonitor Connect sensors.
12
"SMS3R Ratings" on page
56.