COMMUNICATIONS
Modbus RTU Communication
Mod
R/W
RC
Address Name
Bus
464
RW
N
Neg Pwr Enable
465
RW
N
Insul Chk Enable
466
RW
N
Insul Flt Resist
467
RW
N
Insul Alrm Resist
468
RW
N
SubTemp Enable
469
RW
N
SubTemp Fault
Temp
470
RW
N
SubTemp Alarm
Temp
471
RW
N
SubTemp Reset
Type
472
RW
N
SubTemp Retries
473
RW
N
SubTemp Reset
Delay
474
RW
N
Flse Str Enable
475
RW
N
Flse Str Reset Type 0 - Manual (default)
476
RW
N
Flse Str Retry
477
RW
N
Flse Str Rst Dly
478
RW
N
Cycle Fault Enable 0 - Disabled
479
RW
N
Ovr Temp Enable
480
RW
N
Ovr Temp RTD
Type
481
RW
N
Ovr Temp Fault
482
RW
N
Ovr Temp Alarm
483
RW
N
Ovr Temp Delay
484
RW
N
Ovr Temp Reset
Type
485
RW
N
Ovr Temp Retry
486
RW
N
Ovr Temp Rst Dly
487
RW
N
Volt Loss Reset
Type
488
RW
N
Volt Loss Retry
489
RW
N
Volt Loss Rst Dly
46
Choices/Range
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
1 to 2000; default = 500
1 to 3000; default = 1000
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
0 to 150; default = 40
0 to 150; default = 30
0 - Manual (default)
1 - Automatic
1 to 10; default = 3
1 to 43,200; default = 900
0 - Disabled (default)
1 - Enabled
1 - Automatic
1 to 10; default = 3
1 to 43,200; default = 900
1 - Enabled (default)
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
0 - PT100 (default)
1 - PT1000
0 to 200; default = 40
0 to 200; default = 30
1 to 120; default = 5
0 - Disabled (default)
1 - Enabled
1 to 10; default = 3
1 to 43,200; default = 900
0 - Manual (default)
1 - Automatic
1 to 10; default = 3
1 to 43,200; default = 900
Description
Negative power protection enable
Insulation Check Enable
Insulation Resistance Fault Level
Insulation Resistance Alarm Level
SubTemp Motor Protection Enable
SubTemp Fault Trip temperature °C setting
SubTemp Alarm Trip temperature °C setting
SubTemp Reset Method
SubTemp Automatic Reset Attempts allowed
SubTemp Automatic Reset Delay time in seconds
False Start Protection Enable
False Start Reset Method
False Start Automatic Reset - Number of Attempts
False Start Automatic Reset Delay Time
Cycle Fault Protection Enable
RTD Over Temperature Protection Enable
Set the Type of RTD Sensor used
Temperature in °C to Trip a RTD Fault
Temperature in °C to Trip a RTD Alarm
Delay Time in seconds for RTD Fault/Alarm
RTD Over Temperature Reset Method
Number of Automatic Reset Attempts for RTD Over Tem-
perature Fault/Alarm
RTD Over Temperature Automatic Reset Delay Time in
seconds
Voltage Loss Reset Method
Voltage Loss: Number of Automatic Reset Attempts
Voltage Loss Reset Delay Time in seconds