INSTALLATION AND SETUP
Programming: Advanced Setup > I/O Terminals (MT1311/MT2211 only)
Mod
RW
RC
Display Name
bus
471
RW
N
Fault Reset Type
472
RW
N
Reset Retries
473
RW
N
Reset Delay
False Start menu
474
RW
N
Trip
475
RW
N
Fault Reset Type
476
RW
N
Reset Retries
477
RW
N
Reset Delay
Cycle Fault menu
478
RW
N
Trip
Motor Over Temp menu
479
RW
N
Trip/Alarm
480
RW
N
Sensor Type
481
RW
N
Trip Temp
482
RW
N
Alarm Temp
483
RW
N
Time to Trip
484
RW
N
Fault Reset Type
485
RW
N
Reset Retries
486
RW
N
Reset Delay
Programming: Advanced Setup > I/O Terminals
Mod
RW
RC
Display Name
bus
518
RW
N
D1 Contact Type
520
RW
N
D2 Contact Type
524
RW
N
D1/D2 Function
505
RW
N
Control Input
For further information regarding D1/D2 use, refer to
24
Range
0 - Manual (default)
1 - Automatic
1 to 10; default = 3
1 to 43,200; default = 900
0 - Disabled (default)
1 - Enabled
0 - Manual (default)
1 - Automatic
1 to 10; default = 3
1 to 43,200; default = 900
0 - Disabled
1 - Enabled (default)
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
0 - PT100 (default)
1 - PT1000
0 to 200; default = 40
0 to 200; default = 30
1 to 120; default = 5
0 - Disabled (default)
1 - Enabled
1 to 10; default = 3
1 to 43,200; default = 900
Range
Normally Open (default)
Normally Closed
Normally Open
Normally Closed (default)
Auto run / Shutdown
(default)
LO/HI Fill Mode
LO/HI Drain Mode
HOA (default)
HOA W/ Start pushbutton
Start/Stop pushbuttons
"Fill/Drain using Float Switches" on page
Description
SubTemp Reset Method
SubTemp Automatic Reset Attempts allowed
SubTemp Automatic Reset Delay Time in seconds
False Start Protection Enable
False Start Reset Method
False Start Automatic Reset - Number of Attempts
False Start Automatic Reset Delay Time in seconds
Choose the type of response for when a cycle fault condi-
tion is detected.
RTD Over Temperature Protection Enable
Set the Type of RTD Sensor used
Temperature in °C to Trip a RTD Fault
Temperature in °C to Trip a RTD Alarm
Delay Time in seconds for RTD Fault/Alarm
RTD Over Temperature Reset Method
Number of Automatic Reset Attempts for RTD Over Tem-
perature Fault/Alarm
RTD Over Temperature Automatic Reset Delay Time in sec-
onds.
(MT1311/MT2211 only)
Description
Choose the intended function of the switch connected to
D1 and SG.
Choose the intended function of the switch connected to
D2 and SG.
Choose the type of action the switches connected to D1
and D2 perform.
Choose the Pilot device type
27.