Mod
R/W
RC
Address Name
Bus
209
R
N
D1 Status
210
R
N
D2 Status
211
R
N
D3 Status
212
R
N
D4 Status
213
R
N
D5 Status
214
R
N
V1/V2 Status
215
R
N
V3/V4 Status
216
R
N
O1 Status
219
R
N
Date
220
221
R
N
Time
222
227
R
N
Power Loss Count 0 to 4,294,967,295
228
R
N
Motor Run Time
229
230
R
N
Power On Time
231
232
R
N
I/O Version
233
234
R
N
Meter Version
235
236
R
N
Display Version
237
238
R
N
I/O Boot Version
239
240
R
N
Meter Boot Version 0 to 999,999
241
242
R
N
Bluetooth Version 0 to 999,999
243
244
R
N
Gate Drive Version 0 to 999,999
245
Choices/Range
0 - Open
1 - Closed
0 - Open
1 - Closed
0 - Open
1 - Closed
0 - Open
1 - Closed
0 - Open
1 - Closed
0 - De-energized
1 - Energized
0 - De-energized
1 - Energized
0 - Open
1 - Closed
MMDDYY
HHMMSS
0 to 4,294,967,295
0 to 4,294,967,295
0 to 999,999
0 to 999,999
0 to 999,999
0 to 999,999
Modbus RTU Communication
Description
Read this address for the status of dry input terminal D1.
Read this address for the status of dry input terminal D2.
Read this address for the status of dry input terminal D3.
Read this address for the status of dry input terminal D4.
Read this address for the status of dry input terminal D5.
Read this address for the status of wet input terminals V1/
V2.
Read this address for the status of wet input terminals
V3/V4.
Read this address for the status of output Relay terminal
O1.
Read the system date. Only the 3 least significant bytes
are used. From least to most significant byte: year, day,
month (0x00MMDDYY).
Read the system time. Only the 3 least significant bytes
are used. From least to most significant byte: second,
hour, day (0x00HHMMSS).
Read the total number of times the unit was power-
cycled.
Read the accumulated amount of motor run time in sec-
onds.
Read the accumulated system power-on time in seconds.
View the I/O device firmware version. Periods are implied
after 2 and 4 right decimal digits (10203 = v01.02.03).
View the Meter device firmware version. Periods are
implied after 2 and 4 right decimal digits (10203 =
v01.02.03).
View the Display device firmware version. Periods are
implied after 2 and 4 right decimal digits (10203 =
v01.02.03).
View the I/O boot loader version. Periods are implied
after 2 and 4 right decimal digits (10203 = v01.02.03).
View Meter boot loader version. Periods are implied after
2 and 4 decimal digits
(10203 = v01.02.03).
View Bluetooth module firmware version. Periods are
implied after 2 and 4 decimal digits (10203 = v01.02.03).
View Gate drive firmware version. Periods are implied
after 2 and 4 decimal digits
(10203 = v01.02.03).
COMMUNICATIONS
41