Memory Back Up

The following table shows the memory back up options for the SLC 5/03, 5/04, and
5/05 processors. Flash EPROMs (Flash Erasable Programmable Read Only Memory)
combine the versatility of EEPROMs (Electrically-Erasable Programmable Read Only
Memory) with the security of UVPROMs (UV-Erasable PROM).
Memory
SLC 5/03
Back Up
(1747-L531,-L532)
Option
• 1747-M11
Flash EPROM
• 1747-M12
• 1747-M13

Battery Handling, Storing, and Transporting (Cat. No. 1747-BA)

Handling
ATTENTION
!
Storing
Store the lithium batteries in a cool, dry environment, typically +20°C to +25°C
(+68°F to +77°F) and 40% to 60% relative humidity.
Transporting
One or Two Batteries - Up to two batteries can be shipped together within the
United States without restriction. Regulations governing shipment to or within other
countries may differ.
Three or More Batteries - Procedures for the transportation of three or more
batteries shipped together within the United States are specified by the Department
of Transportation (DOT) in the Code of Federal Regulations, CFR49,
"Transportation." An exemption to these regulations, DOT - E7052, covers the
(OS302+ only)
(OS302 Series C)
Do not charge the batteries. An explosion could result or the
cells could overheat causing burns. Do not open, puncture,
crush, or otherwise mutilate the batteries. An explosion may
result and/or toxic, corrosive, and flammable liquids would be
exposed
SLC 5/04
(1747-L541, -542, -543)
• 1747-M11
• 1747-M12
(OS401+ only)
• 1747-M13
(OS401 Series C)
Publication 1746-IN009B-MU-P - February 2002
SLC 5/05
(1747-L551, -552, -553)
• 1747-M11
• 1747-M12
• 1747-M13
(OS501 Series C)