Maximum Liquefied Propane Delivery Capacity
In Thousands of BTU/H (0.5 in WC pressure drop)
Length (including fittings)
Pipe Size
10 ft
20 ft
(3 m)
(6 m)
/
in
291
200
1
2
/
in
608
418
3
4
1 in
1,150
787
1
/
in
2,350
1,620
1
4
1
/
in
3,520
2,420
1
2
2 in
6,790
4,660

4.2 Measuring the Inlet Gas Pressure

WARNING
The boiler cannot function properly without sufficient inlet gas pressure. Measuring the inlet gas pressure should be performed by a
licensed professional only.
The inlet gas pressure must be maintained between 3.5 in and 10.5 in WC for natural gas and between 8.0 in and 13.5 in WC for liquefied
propane.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that
system at test pressures in excess of
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing
of the gas supply piping system at test pressures equal to or less than
30 ft
40 ft
50 ft
(9 m)
(12 m)
(15 m)
160
137
122
336
287
255
632
541
480
1,300
1,110
985
1,940
1,660
1,480
3,750
3,210
2,840
/
psi (3.5 kPa).
1
2
60 ft
80 ft
100 ft
(18 m)
(24 m)
(30 m)
110
101
94
231
212
197
434
400
372
892
821
763
1,340
1,230
1,140
2,570
2,370
2,200
/
psi (3.5 kPa).
1
2
125 ft
150 ft
175 ft
(38 m)
(45 m)
(53 m)
89
84
74
185
175
155
349
330
292
716
677
600
1,070
1,010
899
2,070
1,950
1,730
Connecting the Gas Supply
200 ft
250 ft
(60 m)
(76 m)
67
62
140
129
265
243
543
500
814
749
1,570
1,440
49