Navien NFB-175 Mode D'emploi page 88

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Item
3. DHW Call Signal
4. DHW Priority Time*
5. Anti Legionella
Function**
6. DHW control
method
* DHW Priority Time refers to the time duration that the boiler will give
priority to DHW over space heating.
** This function will provide protection from growth of legionella
bacteria in the DHW tank only. It will not protect water supply
piping.
A mixing valve must be installed on the DHW supply line when
this mode is enabled as water temperatures will exceed 140°F
(60°C).
88
Operating the Boiler
Description
Select a device for sensing the DHW
demand.
1. DHW Thermostat
2. DHW Tank Sensor
Default: DHW Thermostat
Set the DHW Priority time.
Setting range: 0 – 180 min
Default: 30 min
Enable or diable the protection against
legionella bacteria.
Setting range: Enabled/Disabled
Default: Disabled
Select a DHW control type.
1:Supply water
2. System Supply water
Default : Supply water
11.3.5 Viewing Error History
To view the error history, press the Menu button (
select "5. Error History".
A list of 10 recent errors are displayed on the screen, with the most
recent error displayed at the top of the list.
Rotate the Command dial (
Press the Command dial (
) to select an error to view detailed
information.
Press the Back button (
) to return to the previous screen or
menu.
The front panel disaplay flashes in red and the error
Note
icon is displayed (flashing) when a level 1 error is
detected. You can press the command dial to enter
error display mode. Boiler operation is maintained
during a level 1 error.
A level 1 error is automatically cleared when the
problem is resolved.
You can press the power button to clear a level1 error.
Then the error is cleared if the problem has been
resolved.
), and then
) to switch between the list of errors.

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Nfb-200

Table des Matières